1MRS755014
SPA-ZC 302
43
Profibus-DPV1/SPA Gateway
Installation and Commissioning Manual
A050343
Fig. 5.4.8.1.-1 Analog Input configuration dialog
The definitions of the analog input signal settings are the following:
Signal name
Description
Slave Address
The slave address of the protection relay or unit
Ch/Cat/Dno
The Channel (Ch), Category (Cat), and the Data number (Dno)
where the specific Analog values are read from the SPA slave
device.
Scaling
Scaling factor, for details see Section 5.4.8.7.
Size
The size of the analog field on Profibus DP. It can be 16 bit or 32
bit, default is 32 bit. This affects the total template size.
In Use
The In Use flag indicates if the parameter was found in the
connected SPA slave device during the initialization phase. In
the Template info Field the In Use flag is marked with number
1. An unselected check box indicates that the parameter was not
found. For details see Section 4.7. In Use flags.
Priority check box By selecting the
Priority
check-box, you can define if the
message should be polled more frequently than other messages.
This is indicated by the letter P (prioritized) after the signal name
in the Template info field. If the signal is not prioritized the letter
N (normal) can be seen in the Template info field. The default is
N. For details, see Section 5.4.8. Template info.
5.4.8.2.
Digital input
When you have opened a template with a digital input into the main window, you
can configure its settings that are shown in the Template info field as follows:
1. Select the signal you want to configure and click
Edit
, or double-click on the
signal.
2. A dialog is opened in which you can modify the settings of that specific signal,
see Fig. 5.4.8.2.-1. The fields that you cannot configure are dimmed.
3. To save the new settings, click
OK
. To cancel, click
Cancel
to close the dialog
to discard all changes.