1MRS755014
SPA-ZC 302
27
Profibus-DPV1/SPA Gateway
Installation and Commissioning Manual
4. Commissioning
This chapter describes the commissioning of the gateway by using Profibus-DPV1/
SPA Configuration Tool (PCT).
The commissioning phase includes following actions in short:
1. Set the gateway to configuration mode.
2. Connect the PC containing the Profibus-DPV1/SPA Configuration Tool to the
gateway.
3. Open a standard configuration and define the SPA addresses and scaling. In a
multislave project, you can import several standard configurations to the
different slave sections in PCT. For more information, refer to Section 4.3.
Multislave configuration.
4. Save the configuration with a new name.
5. Download the configuration and, optionally, the source to the archive.
6. Connect the gateway to the protection relays and start it up.
7. Connect the gateway to the PC again and upload the configuration.
8. Verify that the appropriate In Use flags are checked.
See the following sections for details about the actions.
4.1.
Hardware set-up
The gateway and the PC hardware must be connected and set up properly in order to
perform a successful configuration of the gateway.
If the ordered product package is a SPA-ZC 302-AA or BA, the provided connection
cable (1MRS120541) can be used for configuration purposes if a
gender change
adapter (female-female) is used for the PC connection.
Connect the cable between the COM port on the PC and the SPA protocol port on
the gateway device. If your PC contains only USB ports, you need an USB to COM
port adapter, which can be purchased from any well-equipped computer store.
Fig. 4.1.-1 Configuration arrangement principle
The SPA protocol port setting must be set to RS-232 using the DIP switches as
described in Section 3.3.3.3. DIP switch configuration.
SPA
RS485
RS232
SPA-ZC 302
Profibu
s
RS485
Off-line Acyclic Address
On-line Diagnostics
SPA INTERFACE
RS485 0000000 1111
TTL 0000011 0000
RS232 0111000 0000
+8V 1
EXTERNAL POWER
Uaux
- +
N L
1 2
CE
110...240VAC
110...220VDC
SPA-ZC 302
gateway
To RS-232 PC COM port
ConfigSetup_a