28
1MRS755014
Profibus-DPV1/SPA Gateway
Installation and Commissioning Manual
SPA-ZC 302
Ensure that PCT is set to use the serial port that the cable is connected to. Check this
by selecting
Settings > COM
in the main menu in PCT. For details about PCT, see
Section 5.2. Starting PCT. PCT adjusts the COM port settings of the PC
automatically.
4.2.
New configuration
Before a new configuration is started, you have to select a standard configuration
template from the configurations described in Chapter 6. Standard configuration
templates. Which one you should select, depends on the requirements of the system
in which the protection relay and the gateway device are installed.
When you have selected the standard configuration template, you have to define the
protection relay dependent data and commission the gateway by following the
instructions below:
1. Start the PCT and open the selected standard configuration template by
selecting
File > Open
in the main menu. Select the wanted standard
configuration template and click
Open
, or just double-click on the template you
want.
A050341
Fig. 4.2.-1 Opening the configuration template
Define the address of the SPA slave connected to the gateway by selecting
Slave >
Set Address
and type in the address in the SPA Slave Address dialog,
see Fig. 4.2.-2.
A050295
Fig. 4.2.-2 Setting the SPA Slave Address