![ABB SPA-ZC 302 Скачать руководство пользователя страница 58](http://html.mh-extra.com/html/abb/spa-zc-302/spa-zc-302_installation-and-commissioning-manual_3588058.webp)
58
1MRS755014
Profibus-DPV1/SPA Gateway
Installation and Commissioning Manual
SPA-ZC 302
Radio frequency interference
test
conducted, common mode
IEC 61000-4-6 and IEC
60255-22-6
10 V (rms),
f = 150 kHz…80 MHz
radiated, amplitude-
modulated
IEC 61000-4-3 and IEC
60255-22-3
10 V/m (rms),
f = 80…1000 MHz
radiated, pulse-modulated
ENV 50204
10 V/m, f = 900 MHz
Fast transient disturbance test
IEC 60255-22-4 and
IEC 60255-22-5
power supply
4 kV
Surge immunity test
IEC 61000-4-5
power supply
4 kV, line to earth
2 kV, line to line
Power frequency (50 Hz)
magnetic field
IEC 61000-4-8
300 A/m continuous
Voltage dips and
short interruptions
IEC 61000-4-11
30%, 10 ms
60%, 100 ms
60%, 1000 ms
>90%, 5000 ms
Electromagnetic emission tests
EN 55011 and
IEC 60255-25
conducted RF emission
(mains terminal)
EN 55011, class A
IEC 60255-25
radiated RF emission
EN 55011, class A
IEC 60255-25
CE approval
Complies with the EMC directive 89/336/EEC and the LV
directive 73/23/EEC
Table 7.2.-4
Dimensions and weight
Type
Dimensions [mm]
Weight [g]
SPA-ZC 302
197 x 104 x 50
530
Table 7.2.-3