198 | © 2017 ABB | 1SDH001330R0002 - ECN000058721 Rev. A
Electronic accessories | 5 - Ekip Signalling 4K module
Continued from the previous page
Settings
Circuit-breaker
…
Ground protection
Installation
Main frequency
Modules
…
Functions
Switch On LOCAL
Signalling RESET
Power Controller
…
System
Functions
YO Command
YC Command
Maintenance
The following table describes the programmable actions on the trip unit:
Action
Description
Trip RESET
Resetting of the trip signal.
RESET Energy
Resetting of the energy counters (see the chapter "16 - Ekip Measuring
Measurements", and the paragraph "Energy counters", on page 113).
External Trip
Opening of the circuit-breaker (see the chapter "6 - Menu", and the paragraph
"Advanced menus", on page 48).
Switch On LOCAL
Switching of the connection from remote to local (see the chapter "6 - Menu",
and the paragraph "Settings Menu", on page 49).
Signalling RESET
Resetting of the signals.
YO Command
Opening coil command (see the chapter "6 - Menu", and the paragraph
"Settings Menu", on page 49).
YC Command
Closing coil command (see the chapter "6 - Menu", and the paragraph
"Settings Menu", on page 49).
Turn on SET B
Switching the protections from configuration A to configuration B (see the
chapter "11 - Hi-Touch protections", and the paragraph "Set A-B", on page 87).
The following table shows the path for accessing the Test command of the module:
Test
…
Test CB
Ekip Signalling 2K
(1)
Ekip Signalling 4K
Auto Test
Zone selectivity (68)
(1)
Menu available with module Ekip signalling 2K.
Содержание SACE Emax E1.2
Страница 2: ...ABB SACE Emax 2 2 2017 ABB 1SDH001330R0002 ECN000058721 Rev A ...
Страница 8: ...VI 2017 ABB SACE Emax 2 1SDH001330R0002 ECN000058721 Rev A ...
Страница 9: ...ABB SACE Emax 2 3 2017 ABB 1SDH001330R0002 ECN000058721 Rev A ...
Страница 310: ...ABB SACE Emax 2 304 2017 ABB 1SDH001330R0002 ECN000058721 Rev A Service 1 Power Care ...
Страница 311: ...1SDH001330R0002 ECN000058721 Rev A ...