ABB | SACE Emax 2
Ekip Touch protection trip unit | 6 - Menu
51 | © 2017 ABB | 1SDH001330R0002 - ECN000058721 Rev. A
About Menu
This menu allows you to view information on:
• Mainboard and trip unit (serial number, model, software version, etc.).
• The circuit-breaker (serial number, rated current, configuration with or without neutral, number of poles,
fixed or withdrawable version, state, etc).
• The connected electronic accessories (serial number, model if present, software version if present,
information on state if present, etc).
• Date and time.
Information
Function
Protection unit
It displays:
• Information on Mainboard and trip unit.
• Date and time.
Circuit Breaker
Displays information on the circuit-breaker.
Modules
It displays a list of the electronic accessories connected.
Power Controller
(1)
•
Load input status
: shows the Open/Closed state of the loads
•
Load Active
: shows the Active/Inactive state of the loads.
(1)
Menus available with the Power Controller function enabled (see the Settings Menu- Power Controller).
Measurements Menu
This menu allows you to:
• It open lists of recorded events.
• It display measurements in graphical or numerical form.
• It reset measurements.
The following table shows the submenus and the parameters associated to the menu
Measurements
up
to Level 3 (if present), and the Ekip Touch trip units where they can be found. The options corresponding
to parameters and commands are underlined, to distinguish them from those corresponding to submenus.
Measurements
Options
Trip units
Historicals
•
Trip
: it opens a list of the trip performed.
•
Events
: it opens a list of the recorded events.
•
Measurements
: it opens a list of the dimensions whose history can
be displayed.
Touch
G-Touch
Hi-Touch
G Hi-Touch
Power factor
It displays the power factor measured.
Touch
(1)
G-Touch
Hi-Touch
G Hi-Touch
Frequency
It shows the frequency measured for the voltages.
Energy
•
Energy counters
: it displays the active, reactive and apparent
energies measured.
• Reset counters: it resets the energy counters.
•
Energy RESET
: opens a list of the parameters for programming the
reset of the energy counters (see the chapter "20 - Operating features",
and the paragraph "Functional characteristics", on page 124).
Peak factor
It shows the peak factors measured for the phase currents and the
neutral currents.
Touch
G-Touch
Hi-Touch
G Hi-Touch
Harmonic
Distortion
It opens the
Modify Parameters
page, to enable/disable the alarm
with a peak factor greater than 2.1.
Ekip
Synchrocheck
(2)
It opens a list of the measurements related to the synchronism
function.
Touch
(1)
G-Touch
Hi-Touch
G Hi-Touch
Network
Analyzer
(3)
•
V Sequences
: it shows the last and penultimate positive and
negative voltage sequences measured.
•
V 3s Sequences
: it shows the voltage sequences and unbalance
measured in last the 3 seconds.
•
THD Current
: it shows the measurements of the harmonic
distortion of currents.
•
THD Voltages
: it shows the measurements of the harmonic
distortion of line-to-line voltages.
•
Counters
: it allows you to display the number of events monitored
by the function in the last twenty-four hours and the totals.
•
Waveforms
: it opens a list of the currents and voltages for which an
instantaneous wave form can be displayed.
Hi-Touch
G Hi-Touch
Continued on the next page
Содержание SACE Emax E1.2
Страница 2: ...ABB SACE Emax 2 2 2017 ABB 1SDH001330R0002 ECN000058721 Rev A ...
Страница 8: ...VI 2017 ABB SACE Emax 2 1SDH001330R0002 ECN000058721 Rev A ...
Страница 9: ...ABB SACE Emax 2 3 2017 ABB 1SDH001330R0002 ECN000058721 Rev A ...
Страница 310: ...ABB SACE Emax 2 304 2017 ABB 1SDH001330R0002 ECN000058721 Rev A Service 1 Power Care ...
Страница 311: ...1SDH001330R0002 ECN000058721 Rev A ...