Ekip Dip protection trip unit | 8 - Default parameters
8 - Default parameters
The Ekip Dip trip units are supplied with the following default parameters, some adjustable with the front DIPs
(protections, Frequency, Neutral), other via front bus.
Protection/Parameter
Value
L
1 In; 144 s
S
(1)
Off; 0.1 s
I
4 In
G
(1)
Off; 0.1 s
Frequency
50 Hz (IEC) / 60 Hz (UL)
Neutral
Off (for three-pole circuit breakers).
50 % (for four-pole circuit-breaker)
Hardware Trip
Disabled
Monitor time
5 minutes
Local Bus
Disabled
Alive LED
Disabled (Power-on LED fixed)
Maintenance
Off
(1)
S Protection available with LSI and LSIG versions of the trip unit. G Protection available with LSIG version.