ABB | SACE Emax 2
Mechanical accessories | 3 - Mechanical Interlocks
267 | © 2017 ABB | 1SDH001330R0002 - ECN000058721 Rev. A
3 - Mechanical Interlocks
Mechanical interlocks determine the opening/closing logic between two or three circuit-breakers.
Four types of interlocks are available, usable in both fixed and withdrawable versions.
Mechanical interlock of type A -
Two Circuit-breakers
1
2
O
I
O
O
O
I
The Type A interlock is applicable to two circuit-breakers (normal power emergency power supply).
It allows you never to have two circuit-breakers in the closed position at the same time.
Information on assembly is available on the website http://www.abb.com/abblibrary/DownloadCenter/, in
particular with the kit sheets:
•
for interlock between E1.2circuit-breakers
•
for interlock between E2.2-E4.2-E6.2 circuit-breakers
•
for interlock between one E1.2 circuit-breaker and one E2.2-E4.2-E6.2 circuit-breaker
Mechanical interlock of type B -
Three Circuit-breakers
1
2
3
O
I
O
O
I
O
O
O
O
O
I
O
O
I
I
The Type B interlock is applicable to three circuit-breakers (two normal power su emergency power
supply).
It only allows the closing of the two circuit-breakers of the normal power supply if the circuit-breaker of the
emergency power supply is open. The circuit-breaker of the emergency power supply can be closed only if
the others two are open.
Information on the assembly is available on the website http://www.abb.com/abblibrary/DownloadCenter/, in
particular with the kit sheet
.
Mechanical interlock of type C -
Three Circuit-breakers
1
2
3
O
I
O
O
O
O
O
O
I
O
I
I
O
O
I
I
I
O
I
I
O
The Type C interlock is applicable to three circuit-breakers (two normal power su a bus tie).
It allows the simultaneous closing of one or two circuit-breakers, resulting in two possible types of power
supply of the half busbars:
• power supply from a single transformer (bus tie closed)
• power supply from both transformers (bus tie open)
Information on the assembly is available on the website http://www.abb.com/abblibrary/DownloadCenter/, in
particular with the kit sheet
.
Mechanical interlock of type D -
Three Circuit-breakers
1
2
3
O
I
O
O
O
O
O
O
I
I
O
O
The Type C interlock is applicable to three circuit-breakers (three power supplies on the same bar that must
not operate in parallel)
It allows only one of the three circuit-breakers to be closed.
Information on the assembly is available on the website http://www.abb.com/abblibrary/DownloadCenter/, in
particular with the kit sheet
.
Содержание SACE Emax E1.2
Страница 2: ...ABB SACE Emax 2 2 2017 ABB 1SDH001330R0002 ECN000058721 Rev A ...
Страница 8: ...VI 2017 ABB SACE Emax 2 1SDH001330R0002 ECN000058721 Rev A ...
Страница 9: ...ABB SACE Emax 2 3 2017 ABB 1SDH001330R0002 ECN000058721 Rev A ...
Страница 310: ...ABB SACE Emax 2 304 2017 ABB 1SDH001330R0002 ECN000058721 Rev A Service 1 Power Care ...
Страница 311: ...1SDH001330R0002 ECN000058721 Rev A ...