ABB | SACE Emax 2
78 | © 2017 ABB | 1SDH001330R0002 - ECN000058721 Rev. A
Ekip Touch protection trip unit | 10 - Measuring Pro protections
OF Protection
f13
t
t13
f
OF
Path
Main page - Menu - Advanced
Function
OF protection trips when the line frequency rises above the set threshold.
If the line frequency rises above the activation threshold, the protection trips within a fixed time set by the
user.
NOTE:
the protection is not active for voltages <30V.
Parameters
Here is a list of the available parameters:
Parameter
Description
Enable
To activate/deactivate the protection.
Threshold f13
It defines the frequency value above which the protection is activated (with
reference to the figure above, the threshold is the part of the curve parallel to
the y-axis).
It is represented both as an absolute value (Hertz) and a relative value (fn,
nominal value defined on the trip unit).
Time t13
The delay time between the exceeding of the f13 threshold and the sending of
the opening command (with reference to the figure above, the threshold is the
part of the curve parallel to the x-axis).
OF protection has
StartUp enable
, see page 71.
Via Ekip Connect it is also possible to access the
blocking functions
, see page 72.
RP Protection
P11
t
t11
P
RP
Path
Main page - Menu - Advanced
Function
RP protection trips when the total reverse active power exceeds the reverse active power threshold set.
When the total reverse active power rises above the set threshold, the protection delays for the set time t11
and then opens.
Parameters
Here is a list of the available parameters:
Parameter
Description
Enable
To activate/deactivate the protection.
Threshold P11
It defines the power value for which the protection is activated (with reference
to the figure above, the threshold is the part of the curve parallel to the y-axis).
It is represented both as an absolute value (KW) and a relative value (Sn,
referring to the rated voltage set on the trip unit).
NOTE:
the threshold expressed in Sn is preceded by the sign “- “ in
order to indicate that it refers to reverse power.
Time t11
The delay time between the exceeding of the p11 threshold and the sending of
the opening command (with reference to the figure above, the threshold is the
part of the curve parallel to the x-axis).
RP protection has
StartUp enable
Via Ekip Connect it is also possible to access the
blocking functions
, see page 72.
Содержание SACE Emax E1.2
Страница 2: ...ABB SACE Emax 2 2 2017 ABB 1SDH001330R0002 ECN000058721 Rev A ...
Страница 8: ...VI 2017 ABB SACE Emax 2 1SDH001330R0002 ECN000058721 Rev A ...
Страница 9: ...ABB SACE Emax 2 3 2017 ABB 1SDH001330R0002 ECN000058721 Rev A ...
Страница 310: ...ABB SACE Emax 2 304 2017 ABB 1SDH001330R0002 ECN000058721 Rev A Service 1 Power Care ...
Страница 311: ...1SDH001330R0002 ECN000058721 Rev A ...