ABB | SACE Emax 2
Introduction to Ekip trip units | 1 - Presentation
15 | © 2017 ABB | 1SDH001330R0002 - ECN000058721 Rev. A
Protections
Numerous protection functions are available to protect the circuit-breaker in abnormal conditions of the
installation. The combination of the protection functions varies depending on the type of trip unit, as shown
in the following table:
Dip
Touch
Hi-Touch
G Touch
G Hi-Touch
DISTRIBUTION
GENERATORS
Dip
Touch
Dip Pr.
Touch Pr.
Ekip M. Meas.
Pro
Touch Pr.
Ekip M.
Meas. Pro
Hi-Touch Pr.
Touch Pr.
Ekip M.
Meas. Pro
G Touch Pr.
Touch Pr.
Ekip M.
Meas. Pro
Hi-Touch Pr.
G Touch Pr.
G Hi-
Touch Pr.
External toroid
S.G.R.
Rc
All the protections are described by type:
Type
Available protections
Page
DIP protections
L (+ functions), S (+ functions), I, G
Touch protections
L (+ functions), S (+ functions), I (+ functions), G (+ functions), 2I, MCR, IU 61
Measuring Pro
protections
UV, OV, UF, OF, VU, RP and SC (if the Ekip Synchrocheck module is also
present)
Hi-Touch protections
S2, D (+ functions), UV2, OV2, UF2, OF2, Set A-B
G Touch protections
S(V), RQ, OQ, OP, UP
G Hi-Touch protections ROCOF, S2(V), RQ2
Touch trip units can be connected to an SGR or RC toroid, which allow activation, respectively, of the
Gext
protections (page 244) and
Rc
protections to be activated (page 101).
Содержание SACE Emax E1.2
Страница 2: ...ABB SACE Emax 2 2 2017 ABB 1SDH001330R0002 ECN000058721 Rev A ...
Страница 8: ...VI 2017 ABB SACE Emax 2 1SDH001330R0002 ECN000058721 Rev A ...
Страница 9: ...ABB SACE Emax 2 3 2017 ABB 1SDH001330R0002 ECN000058721 Rev A ...
Страница 310: ...ABB SACE Emax 2 304 2017 ABB 1SDH001330R0002 ECN000058721 Rev A Service 1 Power Care ...
Страница 311: ...1SDH001330R0002 ECN000058721 Rev A ...