UDPCtrlConnCnt4
0 to 4
Number of UDP control client connected on
UDP Group4
UDPStreamStat5
Off
Active
Config Error
Off by client
Client unreachable
UDP data stream status for UDP Group5
UDPCtrlConnCnt5
0 to 4
Number of UDP control client connected on
UDP Group5
UDPStreamStat6
Off
Active
Config Error
Off by client
Client unreachable
UDP data stream status for UDP Group6
UDPCtrlConnCnt6
0 to 4
Number of UDP control client connected on
UDP Group6
UDPCtrlDataErrCnt
0 to 4294967295
Number of times IED has failed to respond for
a command requested on C37.118 or
IEEE1344 over TCP control for UDP
UDPCtrlCfgErrCnt
0 to 4294967295
Number of errors that have occurred due to
incorrect configuration request by the client
over TCP control for UDP
The following describes the various output states:
•
PMUInst1, PMUInst2
– The outputs on these channels show the status of the two
available PMUREPORT instances.
Each status output has the following states:
•
Off – When the component is not in operation.
•
Ready – when it is sending data based on the configuration.
•
ConfigError – if same PMU Id is used for both the instances.
•
Data Invalid – when the PMU is producing an invalid data stream and the data
from it cannot be trusted.
•
TCPConnStatus1-8
– The 8 TCP connection status outputs show if there is an active
TCP connection or not. Each status output has the following states:
•
Off - No active connection.
•
Active - A client is connected and receiving data.
•
TCPCtrlDataErrCnt
- The output shows the number of times the PMU has failed to
send the configuration frame, header frames or data frame on C37.118 or IEEE1344.
•
TCPCtrlCfgErrCnt
- The outputs show the number of errors that have occurred due
to incorrect configuration request by the client. These errors can be due to client
trying to send a wrong PMUId on this link than the one that is configured, or trying
to request an IEEE1344 configuration on C37.118 channel.
•
UDPStreamStat1-6
- The six UDP stream status outputs have the following states:
Section 13
1MRK 511 366-UUS -
Troubleshooting
178
Commissioning manual
Содержание RES670 2.1
Страница 1: ...Relion 670 series Phasor measurement unit RES670 2 1 ANSI Commissioning manual ...
Страница 2: ......
Страница 14: ...8 ...
Страница 56: ...50 ...
Страница 60: ...54 ...
Страница 68: ...62 ...
Страница 86: ...80 ...
Страница 102: ...96 ...
Страница 178: ...172 ...
Страница 200: ...194 ...
Страница 201: ...195 ...