Section 13
Troubleshooting
13.1
Checking the self supervision signals
13.1.1
Checking the self supervision function
13.1.1.1
Determine the cause of an internal failure
This procedure describes how to navigate the menus in order to find the cause of an
internal failure when indicated by the flashing green LED on the HMI module.
Procedure
1.
Display the general diagnostics menu.
Navigate the menus to:
Diagnostics/IED status/General
2.
Scroll the supervision values to identify the reason for the failure.
Use the arrow buttons to scroll between values.
13.1.2
Self supervision HMI data
13.1.2.1
General IED status
The following table shows the general IED status signals.
Table 13:
Signals from the General menu in the diagnostics tree.
Indicated result
Possible reason
Proposed action
Internal fail Off
No problem detected.
None.
Internal fail On
A failure has occurred.
Check the rest of the indicated results to find the
fault.
Internal warning Off
No problem detected.
None.
Internal warning On
A warning has been
issued.
Check the rest of the indicated results to find the
fault.
Time synch Ready
No problem detected.
None.
Time synch Fail
No time synchronization.
Check the synchronization source for problems.
If the problem persists, contact your ABB
representative for service.
Table continues on next page
1MRK 511 366-UUS -
Section 13
Troubleshooting
173
Commissioning manual
Содержание RES670 2.1
Страница 1: ...Relion 670 series Phasor measurement unit RES670 2 1 ANSI Commissioning manual ...
Страница 2: ......
Страница 14: ...8 ...
Страница 56: ...50 ...
Страница 60: ...54 ...
Страница 68: ...62 ...
Страница 86: ...80 ...
Страница 102: ...96 ...
Страница 178: ...172 ...
Страница 200: ...194 ...
Страница 201: ...195 ...