Test of the interactions or combinations that are not configured are not considered in this
instruction.
X1OutRv
ZL
j
j
R
X
X1OutFw
X1InFw
1
RLdOutFw
RLdInFw
RLdOutRv
RLdInRv
2
3
4
X1InRv
IEC09000226_1_en.vsd
IEC09000226 V1 EN
Figure 24:
Operating principle and characteristic of the power swing detection
function (settings parameters in italic)
Where:
RLdInFw =
RLdOutFw · kLdRFw
RLdInRv =
RLdOutRv · kLdRRv
X1OutFw =
(RLdOutFw - RLdInFw)
X1OutRv =
(RLdOutFw - RLdInFw)
11.3.1.1
Verifying the settings
Preconditions
The following output signal shall be configured to binary output available: ZOUT,
measured impedance within outer impedance boundary.
Section 11
1MRK 511 366-UUS -
Testing functionality by secondary injection
100
Commissioning manual
Содержание RES670 2.1