Section 9
Establishing connection and verifying the
IEEE C37.118/1344 communication
9.1
Overview
The IED can support synchrophasor data communication via IEEE C37.118 and/or
IEEE1344 with maximum 8 TCP clients and 6 UDP client groups, simultaneously.
The rear OEM ports are used for IEEE C37.118/1344 communication. The same ports can
also be used for substation bus (IEC 61850-8-1) communication and process bus (IEC
61850-9-2LE) communication where applicable.
In order to establish a connection between PMU and a TCP/UDP client (PDC client), an
Ethernet communication link (e.g. optical fiber) shall be available and the required
parameters on both PMU and the TCP/UDP client shall be set. For the purpose of this
section, an Open PDC tool (PMU Connection Tester) installed on a PC is used as the TCP/
UDP client.
9.2
Setting the PMU station communication (PMU Report)
1.
Check the settings for the PMU Report parameters by navigating to:
Main menu/
Configuration/Communication/Station communication/phasor
measurement/PMU Report/PMUREPORT:1
1.1. Make sure that the operation of at least one PMU instance (e.g. PMU1) is
Enabled
.
1.2. Enable sending the frequency data by setting the parameter
SendFreqInfo
to
Enabled
.
2.
Check the operation of the required phasor channels (PHASORREPORT) by
navigating to:
Main menu/Configuration/Communication/Station
communication/phasor measurement/PMU Report/PHASORREPORT:x
.
1MRK 511 366-UUS -
Section 9
Establishing connection and verifying the IEEE C37.118/1344 communication
65
Commissioning manual
Содержание RES670 2.1
Страница 1: ...Relion 670 series Phasor measurement unit RES670 2 1 ANSI Commissioning manual ...
Страница 2: ......
Страница 14: ...8 ...
Страница 56: ...50 ...
Страница 60: ...54 ...
Страница 68: ...62 ...
Страница 86: ...80 ...
Страница 102: ...96 ...
Страница 178: ...172 ...
Страница 200: ...194 ...
Страница 201: ...195 ...