Instantaneous residual overcurrent protection EFPIOC

M12701-3 v16

The Instantaneous residual overcurrent protection (EFPIOC)
has a low transient overreach and short tripping times to
allow the use for instantaneous earth-fault protection, with the
reach limited to less than the typical eighty percent of the line
at minimum source impedance. EFPIOC is configured to
measure the residual current from the three-phase current
inputs and can be configured to measure the current from a
separate current input.

Directional residual overcurrent protection, four steps
EF4PTOC

M13667-3 v19

Directional residual overcurrent protection, four steps
(EF4PTOC) can be used as main protection for phase-to-
earth faults. It can also be used to provide a system back-up,
for example, in the case of the primary protection being out of
service due to communication or voltage transformer circuit
failure.

EF4PTOC has an inverse or definite time delay independent
for each step.

All IEC and ANSI time-delayed characteristics are available
together with an optional user-defined characteristic.

EF4PTOC can be set to be directional or non-directional
independently for each step.

IDir, UPol and IPol can be independently selected to be either
zero sequence or negative sequence.

A second harmonic blocking can be set individually for each
step.

Directional operation can be combined together with the
corresponding communication logic in permissive or blocking
teleprotection scheme. The current reversal and weak-end
infeed functionality are available as well.

The residual current can be calculated by summing the three-
phase currents or taking the input from the neutral CT.

Four step directional negative phase sequence overcurrent
protection NS4PTOC

GUID-485E9D36-0032-4559-9204-101539A32F47 v6

Four step directional negative phase sequence overcurrent
protection (NS4PTOC) has an inverse or definite time delay
independent for each step separately.

All IEC and ANSI time delayed characteristics are available
together with an optional user defined characteristic.

The directional function is voltage polarized.

NS4PTOC can be set directional or non-directional
independently for each of the steps.

NS4PTOC can be used as main protection for unsymmetrical
fault; phase-phase short circuits, phase-phase-earth short
circuits and single phase earth faults.

NS4PTOC can also be used to provide a system backup for
example, in the case of the primary protection being out of
service due to communication or voltage transformer circuit
failure.

Directional operation can be combined together with
corresponding communication logic in permissive or blocking
teleprotection scheme. The same logic as for directional zero
sequence current can be used. Current reversal and weak-
end infeed functionality are available.

Sensitive directional residual overcurrent and power
protection SDEPSDE

SEMOD171438-5 v6

In isolated networks or in networks with high impedance
earthing, the earth fault current is significantly smaller than
the short circuit currents. In addition to this, the magnitude of
the fault current is almost independent on the fault location in
the network. The protection can be selected to use either the
residual current or residual power component 3U0·3I0·cos 

j

,

for operating quantity with maintained short circuit capacity.
There is also available one nondirectional 3I0 step and one
3U0 overvoltage tripping step.

No specific sensitive current input is needed. Sensitive
directional residual overcurrent and power protection
(SDEPSDE) can be set as low 0.25% of IBase.

Thermal overload protection, one time constant LCPTTR/
LFPTTR

M12020-4 v14

The increasing utilization of the power system closer to the
thermal limits has generated a need of a thermal overload
protection for power lines.

A thermal overload will often not be detected by other
protection functions and the introduction of the thermal
overload protection can allow the protected circuit to operate
closer to the thermal limits.

The three-phase current measuring protection has an I

2

t

characteristic with settable time constant and a thermal
memory. The temperature is displayed in either Celsius or
Fahrenheit, depending on whether the function used is
Thermal overload protection (LCPTTR) (Celsius) or (LFPTTR)
(Fahrenheit).

An alarm level gives early warning to allow operators to take
action well before the line is tripped.

Estimated time to trip before operation, and estimated time to
reclose after operation are presented.

Thermal overload protection, two time constants TRPTTR

M13243-3 v11

If a power transformer reaches very high temperatures the
equipment might be damaged. The insulation within the
transformer will experience forced ageing. As a consequence
of this the risk of internal phase-to-phase or phase-to-earth
faults will increase.

1MRK 511 404-BEN A

Bay control REC670 2.2

 

Product version: 2.2.1

 
 

ABB

29

Содержание Relion REC670

Страница 1: ...RELION 670 SERIES Bay control REC670 Version 2 2 Product guide...

Страница 2: ...2 22 Connection diagrams 45 23 Technical data 46 24 Ordering for customized IED 116 25 Ordering for pre configured IED 127 26 Ordering for Accessories 133 Disclaimer The information in this document i...

Страница 3: ...e and a half breaker diameter Disturbance recording and fault locator are available to allow independent post fault analysis after primary disturbances in case of a failure in the protection system Du...

Страница 4: ...IN LF PTTR 26 SDE PSDE 67N IN UV2 PTUV 27 2 3U SA PTOF 81 f OV2 PTOV 59 2 3U GOP PDOP 32 P SA PFRC 81 df dt GUP PDUP 37 P TR PTTR 49 CV GAPC 2 I U LMB RFLO 21FL FL EC PSCH 85 TR8 ATCC 90 U ECRW PSCH...

Страница 5: ...PTTR 26 C MMXU MET I C MSQI MET Isqi FUF SPVC U I WA1 WA2_VT WA1_VT WA2 LINE_VT LINE_CT1 LINE_CT2 S CILO 3 Control S CSWI 3 Control S XSWI 3 Control S CILO 3 Control S CSWI 3 Control S XSWI 3 Control...

Страница 6: ...F4 PTOC 51N_67N 4 IN GOP PDOP 32 P GUP PDUP 37 P LMB RFLO 21FL FL EC PSCH 85 ECRW PSCH 85 SMP PTRC 94 1 0 Q CRSV 3 Control C MMXU MET I C MSQI MET Isqi C MMXU MET I C MSQI MET Isqi WA1 WA2_VT FUF SPVC...

Страница 7: ...GOP PDOP 32 P GUP PDUP 37 P CV GAPC 2 I U LMB RFLO 21FL FL EC PSCH 85 ECRW PSCH 85 VD SPVC 60 Ud SMP PTRC 94 1 0 CC RBRF 50BF 3I BF VN MMXU MET UN V MMXU MET U V MSQI MET Usqi C MMXU MET I C MSQI MET...

Страница 8: ...ns included in the product by default All parameters should be verified by the customer since these are specific to the system object or application Optional functions and optional IO ordered will not...

Страница 9: ...AAC B386 B38B57718BD2 v13 Table 1 Example of quantities 2 number of basic instances 0 3 option quantities 3 A03 optional function included in packages A03 refer to ordering details IEC 61850 or functi...

Страница 10: ...26 Thermal overload protection one time constant Fahrenheit 0 6 1 C51 1 C52 2 C53 1 C51 TRPTTR 49 Thermal overload protection two time constants 0 6 1 C51 1 C52 2 C53 1 C51 CCRBRF 50BF Breaker failure...

Страница 11: ...6 6 E01 6 E01 6 E01 6 E01 SAPFRC 81 Rate of change of frequency protection 0 6 6 E01 6 E01 6 E01 6 E01 FTAQFVR 81A Frequency time accumulation protection 0 12 Multipurpose protection CVGAPC General c...

Страница 12: ...90 Automatic voltage control for tap changer parallel control 0 4 1 H15 1 H15 2 H18 1 H15 TCMYLTC 84 Tap changer control and supervision 6 binary inputs 0 4 4 4 4 4 TCLYLTC 84 Tap changer control and...

Страница 13: ...D GATE INV LLD OR PULSETIMER RSMEMORY SRMEMORY TIMERSET XOR Basic configurable logic blocks see Table 2 40 420 40 420 40 420 40 420 40 420 ANDQT INDCOMBSPQT INDEXTSPQT INVALIDQT INVERTERQT ORQT PULSET...

Страница 14: ...2 12 12 12 12 INTCOMP Comparator for integer inputs 30 30 30 30 30 REALCOMP Comparator for real inputs 30 30 30 30 30 Table 2 Total number of instances for basic configurable logic blocks Basic config...

Страница 15: ...1 DB_BUS_A 1 DB_BUS_B 1 DB_LINE 1 ABC_LINE 1 AB_TRAFO 1 SCSWI Switch controller 10 SXSWI Circuit switch 9 QCRSV Apparatus control 2 RESIN1 1 RESIN2 59 POS_EVAL Evaluation of position indication 10 XL...

Страница 16: ...1 DB_BUS_A 1 DB_BUS_B 1 DB_LINE 1 ABC_LINE 1 AB_TRAFO 1 SCSWI Switch controller 15 SXSWI Circuit switch 14 QCRSV Apparatus control 2 RESIN1 1 RESIN2 59 POS_EVAL Evaluation of position indication 15 X...

Страница 17: ...aluation of position indication 30 QCBAY Bay control 5 LOCREM Handling of LR switch positions 5 XLNPROXY Proxy for signals from switching device via GOOSE 42 GOOSEXLNRCV GOOSE function block to receiv...

Страница 18: ...ckage Extended configurable logic block Total number of instances AND 180 GATE 49 INV 180 LLD 49 OR 180 PULSETIMER 89 RSMEMORY 40 SLGAPC 74 SRMEMORY 130 TIMERSET 109 VSGAPC 120 XOR 89 1MRK 511 404 BEN...

Страница 19: ...3 3 3 RANGE_XP Measured value expander block 66 66 66 66 66 SSIMG 63 Insulation supervision for gas medium 21 21 21 21 21 SSIML 71 Insulation supervision for liquid medium 3 3 3 3 3 SSCBR Circuit brea...

Страница 20: ...ntrol REC670 Customized REC670 A30 REC670 B30 REC670 C30 REC670 D30 Metering PCFCNT Pulse counter logic 16 16 16 16 16 ETPMMTR Function for energy calculation and demand handling 6 6 6 6 6 1MRK 511 40...

Страница 21: ...ion protocol 1 1 1 1 1 DNPFREC DNP3 0 fault records for TCP IP and EIA 485 communication protocol 1 1 1 1 1 IEC 61850 8 1 IEC 61850 1 1 1 1 1 GOOSEINTLKRCV Horizontal communication via GOOSE for inter...

Страница 22: ...gging 1 1 1 1 1 ALTRK Service tracking 1 1 1 1 1 PRP IEC 62439 3 Parallel redundancy protocol 0 1 1 P23 1 P23 1 P23 1 P23 HSR IEC 62439 3 High availability seamless redundancy 0 1 1 P24 1 P24 1 P24 1...

Страница 23: ...nd weak end infeed logic for distance protection 0 1 1 K01 1 K01 1 K01 1 K01 ZCLCPSCH Local acceleration logic 0 1 1 K01 1 K01 1 K01 1 K01 ECPSCH 85 Scheme communication logic for residual overcurrent...

Страница 24: ...TGRPS Number of setting groups ACTVGRP Parameter setting groups TESTMODE Test mode functionality CHNGLCK Change lock function SMBI Signal matrix for binary inputs SMBO Signal matrix for binary outputs...

Страница 25: ...eature evaluates voltage difference phase angle difference slip frequency and frequency rate of change before issuing a controlled closing of the circuit breaker Breaker closing time is a setting Auto...

Страница 26: ...to each IED and is not dependent on any central function For the station wide interlocking the IEDs communicate via the system wide interbay bus IEC 61850 8 1 or by using hard wired binary inputs out...

Страница 27: ...lel transformers and this is provided for within IEC 61850 8 1 Voltage control includes many extra features such as the possibility to avoid simultaneous tapping of parallel transformers hot stand by...

Страница 28: ...protocols Protocol reporting via IEEE 1344 and C37 118 PMUREPORT GUID 8DF29209 252A 4E51 9F4A B14B669E71AB v4 The phasor measurement reporting block moves the phasor calculations into an IEEE C37 118...

Страница 29: ...NS4PTOC can also be used to provide a system backup for example in the case of the primary protection being out of service due to communication or voltage transformer circuit failure Directional oper...

Страница 30: ...ormally the own breaker is tripped to correct such a situation If the situation persists the surrounding breakers should be tripped to clear the unsymmetrical load situation The Pole discordance prote...

Страница 31: ...ency protection SAPTUF M13349 3 v13 Underfrequency occurs as a result of a lack of generation in the network Underfrequency protection SAPTUF measures frequency with high accuracy and is used for load...

Страница 32: ...t functions Current circuit supervision CCSSPVC compares the residual current from a three phase set of current transformer cores with the neutral point current on a separate input taken from another...

Страница 33: ...be transmitted to the other line end With directional comparison a short operate time of the protection including a channel transmission time can be achieved This short operate time enables rapid auto...

Страница 34: ...our inputs and two outputs One of the outputs is inverted GATE function block is used for whether or not a signal should be able to pass from the input to the output INVERTER function block that inver...

Страница 35: ...ble logic blocks Fixed signal function block FXDSIGN M15322 3 v12 The Fixed signals function FXDSIGN has nine pre set fixed signals that can be used in the configuration of an IED either for forcing t...

Страница 36: ...me to the end of post fault time will be included in the recording Disturbance record will have visible settings from all function instances that are configured in the application configuration tool E...

Страница 37: ...cation function for measured values MVGAPC SEMOD55872 5 v10 Generic communication function for measured values MVGAPC function is used to send the instantaneous value of an analog signal to other syst...

Страница 38: ...ure at a given time This value can either be a measured value taken through sensors or the one calculated by the function This decision is made based on the top oil temperature sensor quality Top oil...

Страница 39: ...he synchronization of the IED when it is a part of a control and a protection system This makes it possible to compare events and disturbance data between all IEDs within a station automation system a...

Страница 40: ...M bus Available communication protocols are IEC 61850 8 1 communication protocol IEC UCA 61850 9 2LE communication protocol LON communication protocol SPA communication protocol IEC 60870 5 103 commun...

Страница 41: ...user defined input signals in monitor direction These function blocks include the FunctionType parameter for each block in the private range and the information number parameter for each input signal...

Страница 42: ...tical to galvanic conversion for connection to a multiplexer These units are designed for 64 kbit s resp 2Mbit s operation The converter is delivered with 19 rack mounting accessories 21 Hardware desc...

Страница 43: ...rest are slaves No special control signal is needed in this case GPS time synchronization module GTM M14851 3 v4 This module includes a GPS receiver used for time synchronization The GPS has one SMA...

Страница 44: ...9 10 47 448 3 17 65 242 1 9 53 255 8 10 07 430 3 16 86 190 5 7 50 428 3 16 86 465 1 18 31 228 6 9 00 482 6 19 00 The H and K dimensions are defined by the 19 rack mounting kit Mounting alternatives M...

Страница 45: ...s for IEC Customized products Connection diagram 670 series 2 2 1MRK002801 AG Connection diagrams for Configured products Connection diagram REC670 2 2 A30X00 1MRK002807 CA Connection diagram REC670 2...

Страница 46: ...t in accordance with the associated main instrument transformers Note that for functions which measure an analogue signal which do not have corresponding primary quantity the 1 1 ratio shall be set fo...

Страница 47: ...r 1 s 30 Ir for 10 s 10 Ir for 1 min 4 Ir continuously Dynamic withstand 250 Ir one half wave Burden 20 mVA at Ir 1 A 150 mVA at Ir 5 A max 350 A for 1 s when COMBITEST test switch is included Voltage...

Страница 48: ...VA at 220 V all values for individual voltage inputs Note All current and voltage data are specified as RMS values at rated frequency M6389 1 v5 Table 13 MIM mA input module Quantity Rated value Nomin...

Страница 49: ...EL 100 250 V EL 20 EL 20 Power consumption 50 W typically Auxiliary DC power in rush 10 A during 0 1 s Binary inputs and outputs IP15844 1 v1 M12576 1 v9 Table 17 BIM Binary input module Quantity Rate...

Страница 50: ...ing settable 1 40 Hz Release settable 1 30 Hz Debounce filter Settable 1 20 ms Maximum 176 binary input channels may be activated simultaneously with influencing factors within nominal range M12573 1...

Страница 51: ...resistive load 0 2 s 1 0 s 30 A 10 A 220 250 V 0 4 A 110 125 V 0 4 A 48 60 V 0 2 A 24 30 V 0 1 A Breaking capacity for AC cos 0 4 250 V 8 0 A 250 V 8 0 A Breaking capacity for DC with L R 40 ms 48 V...

Страница 52: ...sistive load 0 2 s 1 0 s 30 A 10 A 220 250 V 0 4 A 110 125 V 0 4 A 48 60 V 0 2 A 24 30 V 0 1 A Breaking capacity for AC cos j 0 4 250 V 8 0 A 250 V 8 0 A Breaking capacity for DC with L R 40 ms 48 V 1...

Страница 53: ...nce open state 300 k 810 k Test voltage across open contact 1 min No galvanic separation No galvanic separation Current carrying capacity Continuous 5 A 5 A 1 0 s 10 A 10 A Making capacity at capaciti...

Страница 54: ...Trip and Signal relays Binary outputs 24 Max system voltage 250 V AC DC Test voltage across open contact 1 min 1000 V rms Current carrying capacity Per relay continuous Per relay 1 s Per process conne...

Страница 55: ...Restart time 300 s Table 27 Frequency influence reference standard IEC 60255 1 Dependence on Within nominal range Influence Frequency dependence operate value fr 2 5 Hz for 50 Hz fr 3 0 Hz for 60 Hz...

Страница 56: ...test 150 300 V 50 Hz IEC 60255 26 Zone A Conducted common mode immunity test 15 Hz 150 kHz IEC 61000 4 16 Class IV Power frequency magnetic field test 1000 A m 3 s 100 A m cont IEC 61000 4 8 Class V P...

Страница 57: ...humidity 93 IEC 60068 2 78 Damp heat test cyclic Test Db for 6 cycles at 25 to 55 C and humidity 93 to 95 1 cycle 24 hours IEC 60068 2 30 Table 31 CE compliance Test According to Immunity EN 60255 26...

Страница 58: ...900 V Maximum continuous power U Trip2 SeriesResistor 200 W Operate time at 0 to 10 x Ud Min 5 ms Max 15 ms Reset time at 10 x Ud to 0 Min 75 ms Max 95 ms Critical impulse time 2 ms typically at 0 to...

Страница 59: ...ty Range Accuracy Signal frequency 0 1 x fr 1 0 TVE Signal magnitude Voltage phasor Current phasor 0 1 1 2 x Ur 0 5 2 0 x Ir Phase angle 180 Harmonic distortion 10 from 2nd 50th Interfering signal Mag...

Страница 60: ...f IBase Operate time at 0 to 2 x Iset Min 15 ms Max 25 ms Reset time at 2 x Iset to 0 Min 15 ms Max 25 ms Critical impulse time 10 ms typically at 0 to 2 x Iset Operate time at 0 to 10 x Iset Min 5 ms...

Страница 61: ...7 Operate time start non directional at 0 to 2 x Iset Min 15 ms Max 30 ms Reset time start non directional at 2 x Iset to 0 Min 15 ms Max 30 ms Operate time start non directional at 0 to 10 x Iset Min...

Страница 62: ...5 Table 156 and Table 157 16 curve types See Table 155 Table 156 and Table 157 Second harmonic blocking 5 100 of fundamental 2 0 of Ir Minimum polarizing voltage 1 100 of UBase 0 5 of Ur Minimum polar...

Страница 63: ...teristic angle RCA 180 to 180 degrees 2 0 degrees Operate current for directional release 1 100 of IBase For RCA 60 degrees 2 5 of Ir at I Ir 2 5 of I at I Ir Minimum polarizing voltage 1 100 of UBase...

Страница 64: ...0 5 of U at U Ur Operate time for non directional residual overcurrent at 0 to 2 x Iset Min 40 ms Max 65 ms Reset time for non directional residual overcurrent at 2 x Iset to 0 Min 40 ms Max 65 ms Ope...

Страница 65: ...F 2 0 C 4 0 F Operate temperature 0 300 C 0 600 F 2 0 C 4 0 F Reset level temperature 0 300 C 0 600 F 2 0 C 4 0 F M13266 2 v8 Table 42 Thermal overload protection two time constants TRPTTR Function R...

Страница 66: ...reater Additional time delay for a second back up trip at 0 to 2 x Iset 0 000 60 000 s 0 2 or 20 ms whichever is greater Time delay for alarm for faulty circuit breaker 0 000 60 000 s 0 2 or 15 ms whi...

Страница 67: ...degrees 2 0 degrees Operate time start at 0 5 x Sr to 2 x Sr and k 0 000 Min 10 ms Max 25 ms Reset time start at 2 x Sr to 0 5 x Sr and k 0 000 Min 35 ms Max 55 ms Independent time delay to operate f...

Страница 68: ...of S at S Sr Operate value voltage protection function for harmonic overload Definite time 10 500 0 5 of Ur at U Ur 0 5 of U at U Ur Operate value voltage protection function for harmonic overload Inv...

Страница 69: ...e types See tables 155 and 156 Minimum operate time for inverse time characteristics 0 00 60 00 s 0 2 or 35 ms whichever is greater High voltage limit voltage dependent operation 30 0 100 0 of UBase 1...

Страница 70: ...00 6000 00 s 0 2 or 40ms whichever is greater Definite time delay step 2 at 1 2 x Uset to 0 0 000 60 000 s 0 2 or 40ms whichever is greater Minimum operate time inverse characteristics 0 000 60 000 s...

Страница 71: ...s whichever is greater Definite time delay high step step 2 at 0 to 1 2 x Uset 0 000 60 000 s 0 2 or 45 ms whichever is greater Minimum operate time Inverse characteristics 0 000 60 000 s 0 2 or 45 ms...

Страница 72: ...15 ms Max 30 ms Operate time start at 0 to 1 2 x Uset Min 20 ms Max 35 ms Reset time start at 1 2 x Uset to 0 Min 5 ms Max 25 ms Critical impulse time 10 ms typically at 0 to 2 x Uset Impulse margin...

Страница 73: ...chever is greater Time delay for enabling the functions after restoration 0 000 60 000 s 0 2 or 35 ms whichever is greater Operate time delay when disconnecting all three phases 0 000 60 000 s 0 2 or...

Страница 74: ...f Ubase UMin 50 150 of Ubase Exponent 0 0 5 0 tMax 0 010 60 000 s tMin 0 010 60 000 s 1 0 or 100 ms whichever is greater Exponent U UMin t tMax tMin tMin UNom UMin EQUATION1182 V1 EN US Equation 3 U U...

Страница 75: ...tion Range or value Accuracy Operate value frequency high limit level at symmetrical three phase voltage 35 00 90 00 Hz 2 0 mHz Operatevalue frequency low limit level at symmetrical three phase voltag...

Страница 76: ...Multipurpose protection M13095 2 v8 1MRK 511 404 BEN A Bay control REC670 2 2 Product version 2 2 1 76 ABB...

Страница 77: ...set to 0 step 1 2 0 00 6000 00 s 0 2 or 35 ms whichever is greater Overcurrent non directional Start time at 0 to 2 x Iset Min 15 ms Max 30 ms Reset time at 2 x Iset to 0 Min 15 ms Max 30 ms Start tim...

Страница 78: ...ble 163 Undervoltage Inverse time characteristics see table 164 3 curve types See table 164 High and low voltage limit voltage dependent operation step 1 2 1 0 200 0 of UBase 1 0 of Ur at U Ur 1 0 of...

Страница 79: ...ction CVGAPC continued Function Range or value Accuracy Undervoltage Critical impulse time 10 ms typically at 1 2 x Uset to 0 8 x Uset Impulse margin time 15 ms typically 1MRK 511 404 BEN A Bay contro...

Страница 80: ...perate current zero sequence 1 100 of IBase 0 5 of Ir Operate voltage negative sequence 1 100 of UBase 0 5 of Ur Operate current negative sequence 1 100 of IBase 0 5 of Ir Operate voltage change level...

Страница 81: ...fuse failure at 1 x Ur to 0 Min 5 ms Max 15 ms Reset time block of main fuse failure at 0 to 1 x Ur Min 15 ms Max 30 ms Operate value alarm for pilot fuse failure 10 0 80 0 of UBase 0 5 of Ur Reset r...

Страница 82: ...tween bus and line for synchronizing 15 30 degrees 2 0 degrees Breaker closing pulse duration 0 050 1 000 s 0 2 or 15 ms whichever is greater tMaxSynch which resets synchronizing function if no close...

Страница 83: ...or 15 ms whichever is greater Circuit breaker closing pulse duration tPulse 0 000 60 000 s 0 2 or 15 ms whichever is greater Reclaim time tReclaim 0 00 6000 00 s 0 2 or 15 ms whichever is greater Maxi...

Страница 84: ...se Load voltage auto correction 20 0 20 0 of UBase Duration time for the reverse action block signal 30 6000 s 0 2 or 600 ms whichever is greater Current limit for reverse action block 0 100 of I1Base...

Страница 85: ...tion change before the value is accepted 1 60 s 0 2 or 200 ms whichever is greater Tap changer constant time out 1 120 s 0 2 or 200 ms whichever is greater Raise lower command output pulse duration 0...

Страница 86: ...is greater Operation mode of unblocking logic Off NoRestart Restart M16039 1 v16 Table 68 Current reversal and weak end infeed logic for distance protection ZCRWPSCH Function Range or value Accuracy...

Страница 87: ...r value 0 000 60 000 s 0 2 or 35 ms whichever is greater M16051 2 v11 Table 71 Current reversal and weak end infeed logic for residual overcurrent protection ECRWPSCH Function Range or value Accuracy...

Страница 88: ...B instances Function Quantity with cycle time 3 ms 8 ms 100 ms STARTCOMB 32 GUID 3AB1EE95 51BF 4CC4 99BD F4ECDAACB75A v1 Table 75 Number of TMAGAPC instances Function Quantity with cycle time 3 ms 8 m...

Страница 89: ...ms 100 ms LLD 10 10 20 GUID 35A795D7 A6BD 4669 A023 43C497DBFB01 v3 Table 83 Number of OR instances Logic block Quantity with cycle time 3 ms 8 ms 100 ms OR 78 60 160 GUID E05E5FB1 23E7 4816 84F2 1FB...

Страница 90: ...SPQT instances Logic block Quantity with cycle time 3 ms 8 ms 100 ms INDCOMBSPQT 10 10 GUID C1E61AE5 22CF 4198 97CF 8C8043EE96D2 v1 Table 91 Number of INDEXTSPQT instances Logic block Quantity with cy...

Страница 91: ...41562FB 6149 495B 8A63 200DF16A5590 v1 Table 97 Number of SRMEMORYQT instances Logic block Quantity with cycle time 3 ms 8 ms 100 ms SRMEMORYQT 10 30 GUID B6231B97 05ED 40E8 B735 1E1A50FDB85F v1 Table...

Страница 92: ...mber of B16I instances Function Quantity with cycle time 3 ms 8 ms 100 ms B16I 6 4 8 GUID 3820F464 D296 4CAD 8491 F3F997359D79 v1 Table 102 Number of BTIGAPC instances Function Quantity with cycle tim...

Страница 93: ...9 9 s 0 2 or 250 ms whichever is greater Table 106 Number of TEIGAPC instances Function Quantity with cycle time 3 ms 8 ms 100 ms TEIGAPC 4 4 4 GUID CEA332FF 838D 42B7 AEFC C1E87809825E v2 Table 107 N...

Страница 94: ...0 1 4 0 x Ir 0 5 of Sr at S 0 5 x Sr 0 5 of S at S 0 5 x Sr 100 to 220 V 0 5 2 0 x Ir 0 2 of S Power factor cos 10 to 300 V 0 1 4 0 x Ir 0 02 100 to 220 V 0 5 2 0 x Ir 0 01 GUID 5E04B3F9 E1B7 4974 9C...

Страница 95: ...0 5 Ir 0 5 degrees at 0 5 Ir I 4 0 Ir GUID 47094054 A828 459B BE6A D7FA1B317DA7 v6 Table 114 Voltage sequence measurement VMSQI Function Range or value Accuracy Voltage positive sequence U1 10 to 300...

Страница 96: ...rate 1 kHz at 50 Hz 1 2 kHz at 60 Hz Recording bandwidth 5 300 Hz GUID F034B396 6600 49EF B0A5 8ED96766A6A0 v7 Table 117 Insulation supervision for gas medium function SSIMG Function Range or value A...

Страница 97: ...greater GUID B6799420 D726 460E B02F C7D4F1937432 v8 Table 119 Circuit breaker condition monitoring SSCBR Function Range or value Accuracy Alarm level for open and close travel time 0 200 ms 3 ms Alar...

Страница 98: ...122 Event list Function Value Buffer capacity Maximum number of events in the list 1000 Resolution 1 ms Accuracy Depending on time synchronizing M13765 1 v5 Table 123 Indications Function Value Buffer...

Страница 99: ...8328 754C238F4AD0 v3 Table 127 Event counter with limit supervision L4UFCNT Function Range or value Accuracy Counter value 0 65535 Max count up speed 30 pulses s 50 duty cycle GUID F5E124E3 0B85 41AC...

Страница 100: ...le time for report of counter value 1 3600 s SEMOD153707 2 v5 Table 130 Function for energy calculation and demand handling ETPMMTR Function Range or value Accuracy Energy metering kWh Export Import k...

Страница 101: ...00 38400 Bd GUID E8B5405C 241C 4DC2 8AB1 3FA77343A4DE v2 Table 132 IEC 61850 9 2 communication protocol Function Value Protocol IEC 61850 9 2 Communication speed for the IEDs 100BASE FX M11927 1 v2 Ta...

Страница 102: ...iber diameter Glass fiber 62 5 125 mm Plastic fiber 1 mm depending on optical budget calculation SEMOD158710 2 v2 Table 138 Galvanic RS485 communication module Quantity Range or value Communication sp...

Страница 103: ...m 50 mile 26 dB typical distance 110 km 68 mile Graded index multimode 50 125 mm 9 dB typical distance about 2 km 1 mile Optical connector Type ST Type FC PC Type FC PC Protocol C37 94 C37 94 implemen...

Страница 104: ...otective earthed Overvoltage category III Pollution degree 2 normally only non conductive pollution occurs except that occasionally a temporary conductivity caused by condensation is to be expected Co...

Страница 105: ...ommunication ports NUM 4 Ethernet ports 1 Basic 3 Optional Ethernet connection type SFP Optical LC or Galvanic RJ45 Carrier modules supported OEM LDCM GUID 4876834C CABB 400B B84B 215F65D8AF92 v2 Tabl...

Страница 106: ...ock BC Ordinary Clock OC Transparent Clock TC Accuracy According to standard IEC IEEE 61850 9 3 Number of nodes According to standard IEC IEEE 61850 9 3 Ports supported All rear Ethernet ports SEMOD55...

Страница 107: ...litude modulated low level high level 1 3 Vpp 3 x low level max 9 Vpp Supported formats IRIG B 00x IRIG B 12x Accuracy 10 s for IRIG B 00x and 100 s for IRIG B 12x Input impedance 100 k ohm Optical co...

Страница 108: ...IEEE C37 112 2 0 or 40 ms whichever is greater ANSI Extremely Inverse A 28 2 B 0 1217 P 2 0 tr 29 1 ANSI Very inverse A 19 61 B 0 491 P 2 0 tr 21 6 ANSI Normal Inverse A 0 0086 B 0 0185 P 0 02 tr 0 4...

Страница 109: ...PR TR t k I CR EQUATION1253 SMALL V1 EN US I Imeasured Iset k 0 05 999 in steps of 0 01 A 0 005 200 000 in steps of 0 001 B 0 00 20 00 in steps of 0 01 C 0 1 10 0 in steps of 0 1 P 0 005 3 000 in step...

Страница 110: ...10 k 2 00 1 5 x Iset I 20 x Iset ANSI IEEE C37 112 5 0 or 160 ms whichever is greater ANSI Extremely Inverse A 28 2 B 0 1217 P 2 0 tr 29 1 ANSI Very inverse A 19 61 B 0 491 P 2 0 tr 21 6 ANSI Normal...

Страница 111: ...PR TR t k I CR EQUATION1253 SMALL V1 EN US I Imeasured Iset k 0 05 999 in steps of 0 01 A 0 005 200 000 in steps of 0 001 B 0 00 20 00 in steps of 0 01 C 0 1 10 0 in steps of 0 1 P 0 005 3 000 in step...

Страница 112: ...ely Inverse A 0 0515 B 0 1140 P 0 02 tr 4 85 ANSI Long Time Extremely Inverse A 64 07 B 0 250 P 2 0 tr 30 ANSI Long Time Very Inverse A 28 55 B 0 712 P 2 0 tr 13 46 ANSI Long Time Inverse A 0 086 B 0...

Страница 113: ...k t U U U IECEQUATION2423 V2 EN US k 0 05 1 10 in steps of 0 01 Type C curve 3 0 480 0 035 32 0 5 n k t U U U IECEQUATION2421 V1 EN US k 0 05 1 10 in steps of 0 01 Programmable curve P k A t D U U B C...

Страница 114: ...0 480 0 055 32 0 5 k t U U U EQUATION1432 SMALL V1 EN US U Uset U Umeasured k 0 05 1 10 in steps of 0 01 Programmable curve P k A t D U U B C U EQUATION1433 SMALL V1 EN US U Uset U Umeasured k 0 05 1...

Страница 115: ...U EQUATION1437 SMALL V2 EN US k 0 05 1 10 in steps of 0 01 Type C curve 3 0 480 32 0 5 0 035 t k U U U EQUATION1438 SMALL V2 EN US k 0 05 1 10 in steps of 0 01 Programmable curve P k A t D U U B C U E...

Страница 116: ...D1ARGN1N1XXXXXXX KKKXXHKKLAGXSY Product definition Differential protection REC670 2 2 F00 X00 A 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Impedance protection B 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 C...

Страница 117: ...hermal overload protection one time constant Celsius LCPTTR 1MRK005911 BA 8 0 6 Thermal overload protection one time constant Fahrenheit LFPTTR 1MRK005911 AA 9 0 6 Thermal overload protection two time...

Страница 118: ...ction CVGAPC 1MRK005915 AA 1 0 9 Table 181 General calculation Position 1 S Table 182 General calculation functions Function Function identification Ordering no Position Available qty Selected qty Not...

Страница 119: ...LTC or TCLYLTC must be ordered Automatic voltage control for tapchanger parallel control TR8ATCC 1MRK005917 PC 9 0 4 Tap changer control and supervision 6 binary inputs TCMYLTC 1MRK005917 DB 10 0 4 Ta...

Страница 120: ...rules First local HMI user dialogue language HMI language English IEC 1MRK002930 AA B1 Additional local HMI user dialogue language No additional HMI language X0 HMI language English US 1MRK002920 UB...

Страница 121: ...Table 199 Human machine interface selection Human machine hardware interface Case size Ordering no Selection Notes and rules Medium size graphic display IEC keypad symbols 1 2 x 19 IEC 3 4 x 19 IEC 1...

Страница 122: ...7 TRM 3IM 5A 4IP 5A 5U 110 220V 50 60Hz compression terminals 1MRK002247 EB A18 A18 TRM 10I 1A 2U 110 220V 50 60Hz compression terminals 1MRK002247 FA A19 A19 TRM 10I 5A 2U 110 220V 50 60Hz compressio...

Страница 123: ...ng two 2 TRM 5 5 4 4 5 1 2 x 19 rack casing one 1 TRM 3 3 3 1 3 including a combination of maximum four modules of type BOM SOM and MIM Table 202 Maximum quantity of I O modules with ringlug terminals...

Страница 124: ...8 48 60VDC 50mA 1MRK000508 AD C1 C1 C1 C1 C1 C1 C1 C1 C1 C1 C1 C1 C1 C1 BIM 16 inputs RL110 110 125VDC 50mA 1MRK000508 BD D1 D1 D1 D1 D1 D1 D1 D1 D1 D1 D1 D1 D1 D1 BIM 16 inputs RL220 220 250VDC 50mA...

Страница 125: ...173 AD V V V V V V V V V V V V V V IOM with MOV 8 inputs 10 2 outputs RL110 110 125VDC 50mA 1MRK000173 BD W W W W W W W W W W W W W W IOM with MOV 8 inputs 10 2 outputs RL220 220 250VDC 50mA 1MRK00017...

Страница 126: ...et module in P30 6 Ethernet SFP RJ45 connector 1MRK005500 BA P p p p p p Optical Ethernet module 1MRK002266 EA H Serial SPA LON DNP IEC 60870 5 103 plastic interface 1MRK001608 AB L Serial SPA LON DNP...

Страница 127: ...2 2 A30X00 A02H02 B1A3 AC CA B A3X0 CDAB1RGN1N1XXXXXXX KKKXXHKKLAGXSY Using the code of each position 1 11 specified as REC670 1 2 2 3 3 4 4 5 6 7 7 8 9 9 9 10 10 10 10 10 10 10 10 11 11 11 11 11 11 1...

Страница 128: ...Autorecloser 3 circuit breakers 1MRK004001 GF H06 Voltage control single transformer 1MRK004001 GL H11 H11 and H15 only in A30 B30 D30 H16 and H18 only in C30 Only one type of voltage control can be...

Страница 129: ...P40 X401 P41 X411 No Transformer input module included X0 X0 Only valid if IEC 61850 9 2 Process bus communication is selected TRM 9I 1A 3U 110 220V 50 60Hz compression terminals 1MRK002247 BG A3 Only...

Страница 130: ...50mA 1MRK000508 AD C1 C1 C1 C1 C1 C1 C1 C1 C1 C1 C1 C1 C1 BIM 16 inputs RL110 110 125VDC 50mA 1MRK000508 BD D1 D1 D1 D1 D1 D1 D1 D1 D1 D1 D1 D1 D1 BIM 16 inputs RL220 220 250VDC 50mA 1MRK000508 CD E1...

Страница 131: ...inputs 10 2 outputs RL110 110 125VDC 50mA 1MRK000173 BD W W W W W W W W W W W W IOM with MOV 8 inputs 10 2 outputs RL220 220 250VDC 50mA 1MRK000173 CD Y Y Y Y Y Y Y Y Y Y Y Y mA input module MIM 6 ch...

Страница 132: ...connector 1MRK005500 BA p p p p p p Optical Ethernet module 1MRK002266 EA H Serial SPA LON DNP IEC 60870 5 103 plastic interface 1MRK001608 AB L Serial SPA LON DNP IEC 60870 5 103 plastic glass inter...

Страница 133: ...tral on current circuits ordering number RK926 315 AK Single breaker Single or Three Phase trip with external neutral on current circuits ordering number RK926 315 AC Multi breaker Single or Three Pha...

Страница 134: ...10 A Combiflex socket on one end must be used SEMOD130267 5 v6 Mounting kit Ordering number Side by side mounting kit Quantity 1MRK 002 420 Z Configuration and monitoring tools IP15162 1 v2 M15042 3...

Страница 135: ...on 2 IEC Quantity 1MRK 511 393 UEN Communication protocol manual IEC 60870 5 103 IEC Quantity 1MRK 511 394 UEN Communication protocol manual LON IEC Quantity 1MRK 511 395 UEN Communication protocol ma...

Страница 136: ...series manuals Document numbers Operation manual IEC 1MRK 500 127 UEN ANSI 1MRK 500 127 UUS Engineering manual IEC 1MRK 511 398 UEN ANSI 1MRK 511 398 UUS Installation manual IEC 1MRK 514 026 UEN ANSI...

Страница 137: ...137...

Страница 138: ...AB Grid Automation Products 721 59 V ster s Sweden Phone 46 0 21 32 50 00 abb com protection control Copyright 2017 ABB All rights reserved Specifications subject to change without notice 1MRK 511 404...

Отзывы: