Maximum 176 binary input channels may
be activated simultaneously with influencing
factors within nominal range.
M12318-1 v8
Table 20. IOM - Binary input/output module contact data (reference standard: IEC 61810-2)
Function or quantity
Trip and signal relays
Fast signal relays (parallel
reed relay)
Binary outputs
10
2
Max system voltage
250 V AC, DC
250 V DC
Test voltage across open contact, 1 min
1000 V rms
800 V DC
Current carrying capacity
Per relay, continuous
Per relay, 1 s
Per process connector pin, continuous
8 A
10 A
12 A
8 A
10 A
12 A
Making capacity at inductive load with L/R > 10 ms
0.2 s
1.0 s
30 A
10 A
0.4 A
0.4 A
Making capacity at resistive load
0.2 s
1.0 s
30 A
10 A
220–250 V/0.4 A
110–125 V/0.4 A
48–60 V/0.2 A
24–30 V/0.1 A
Breaking capacity for AC, cos φ > 0.4
250 V/8.0 A
250 V/8.0 A
Breaking capacity for DC with L/R < 40 ms
48 V/1 A
110 V/0.4 A
125 V/0.35 A
220 V/0.2 A
250 V/0.15 A
48 V/1 A
110 V/0.4 A
125 V/0.35 A
220 V/0.2 A
250 V/0.15 A
Maximum capacitive load
-
10 nF
Maximum 72 outputs may be activated
simultaneously with influencing factors
within nominal range. After 6 ms an
additional 24 outputs may be activated.
The activation time for the 96 outputs must
not exceed 200 ms. 48 outputs can be
activated during 1 s. Continued activation
is possible with respect to current
consumption but after 5 minutes the
temperature rise will adversely affect the
hardware life. Maximum two relays per
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1