![ABB Relion REC670 Скачать руководство пользователя страница 101](http://html1.mh-extra.com/html/abb/relion-rec670/relion-rec670_product-manual_3381059101.webp)
Station communication
M15031-1 v8
Table 131. Communication protocols
Function
Value
Protocol
IEC 61850-8-1
Communication speed for the IEDs
100BASE-FX
Protocol
IEC 60870–5–103
Communication speed for the IEDs
9600 or 19200 Bd
Protocol
DNP3.0
Communication speed for the IEDs
300–115200 Bd
Protocol
TCP/IP, Ethernet
Communication speed for the IEDs
100 Mbit/s
Protocol
LON
Communication speed for the IEDs
1.25 Mbit/s
Protocol
SPA
Communication speed for the IEDs
300–38400 Bd
GUID-E8B5405C-241C-4DC2-8AB1-3FA77343A4DE v2
Table 132. IEC 61850-9-2 communication protocol
Function
Value
Protocol
IEC 61850-9-2
Communication speed for the IEDs
100BASE-FX
M11927-1 v2
Table 133. LON communication protocol
Function
Value
Protocol
LON
Communication speed
1.25 Mbit/s
M11901-1 v2
Table 134. SPA communication protocol
Function
Value
Protocol
SPA
Communication speed
300, 1200, 2400, 4800, 9600, 19200 or 38400 Bd
Slave number
1 to 899
M11921-1 v4
Table 135. IEC 60870-5-103 communication protocol
Function
Value
Protocol
IEC 60870-5-103
Communication speed
9600, 19200 Bd
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
ABB
101