![ABB Relion REC670 Скачать руководство пользователя страница 66](http://html1.mh-extra.com/html/abb/relion-rec670/relion-rec670_product-manual_3381059066.webp)
M12353-1 v14
Table 43. Breaker failure protection CCRBRF
Function
Range or value
Accuracy
Operate phase current
(5-200)% of
lBase
±1.0% of I
r
at I
£
I
r
±1.0% of I at I > I
r
Reset ratio, phase current
> 95%
-
Operate residual current
(2-200)% of
lBase
±1.0% of I
r
at I
£
I
r
±1.0% of I at I > I
r
Reset ratio, residual current
> 95%
-
Phase current level for blocking of contact function (5-200)% of
lBase
±1.0% of I
r
at I
£
I
r
±1.0% of I at I > I
r
Reset ratio
> 95%
-
Operate time for current detection
10 ms typically
-
Reset time for current detection
15 ms maximum
-
Time delay for re-trip at 0 to 2 x I
set
(0.000-60.000) s
±0.2% or ±15 ms whichever is greater
Time delay for back-up trip at 0 to 2 x I
set
(0.000-60.000) s
±0.2% or ±15 ms whichever is greater
Time delay for back-up trip at multi-phase start at
0 to 2 x I
set
(0.000-60.000) s
±0.2% or ±20 ms whichever is greater
Additional time delay for a second back-up trip at
0 to 2 x I
set
(0.000-60.000) s
±0.2% or ±20 ms whichever is greater
Time delay for alarm for faulty circuit breaker
(0.000-60.000) s
±0.2% or ±15 ms whichever is greater
M12350-1 v12
Table 44. Stub protection STBPTOC
Function
Range or value
Accuracy
Operating current
(5-2500)% of
IBase
±
1.0% of I
r
at I ≤ I
r
±
1.0% of I at I > I
r
Reset ratio
> 95% at (50-2500)% of
IBase
-
Independent time delay at 0 to 2 x I
set
(0.000-60.000) s
±
0.2% or
±
30 ms whichever is greater
Operate time, start at 0 to 2 x I
set
Min. = 10 ms
Max. = 20 ms
-
Reset time, start at 2 x I
set
to 0
Min. = 10 ms
Max. = 20 ms
-
Critical impulse time
10 ms typically at 0 to 2 x I
set
-
Impulse margin time
15 ms typically
-
M13279-1 v10
Table 45. Pole discordance protection CCPDSC
Function
Range or value
Accuracy
Operate current
(0–100)% of
IBase
±1.0% of I
r
Independent time delay
between trip condition and trip
signal
(0.000-60.000) s
±0.2% or ± 30 ms whichever is greater
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
66
ABB