![ABB Relion REC670 Скачать руководство пользователя страница 59](http://html1.mh-extra.com/html/abb/relion-rec670/relion-rec670_product-manual_3381059059.webp)
Wide area measurement system
GUID-F0BAEBD8-E361-4D50-9737-7DF8B043D66A v4
Table 34. Protocol reporting via IEEE 1344 and C37.118 PMUREPORT
Influencing quantity
Range
Accuracy
Signal frequency
± 0.1 x f
r
≤ 1.0% TVE
Signal magnitude:
Voltage phasor
Current phasor
(0.1–1.2) x U
r
(0.5–2.0) x I
r
Phase angle
± 180°
Harmonic distortion
10% from 2nd – 50th
Interfering signal:
Magnitude
Minimum frequency
Maximum frequency
10% of fundamental signal
0.1 x f
r
1000 Hz
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
ABB
59