![ABB Relion REC670 Скачать руководство пользователя страница 81](http://html1.mh-extra.com/html/abb/relion-rec670/relion-rec670_product-manual_3381059081.webp)
GUID-E2EA8017-BB4B-48B0-BEDA-E71FEE353774 v5
Table 63. Fuse failure supervision VDSPVC
Function
Range or value
Accuracy
Operate value, block of main fuse failure
(10.0-80.0)% of UBase
±0.5% of Ur
Reset ratio
<110%
Operate time, block of main fuse failure at 1 x U
r
to 0
Min. = 5 ms
–
Max. = 15 ms
Reset time, block of main fuse failure at 0 to 1 x U
r
Min. = 15 ms
–
Max. = 30 ms
Operate value, alarm for pilot fuse failure
(10.0-80.0)% of UBase
±0.5% of Ur
Reset ratio
<110%
–
Operate time, alarm for pilot fuse failure at 1 x U
r
to 0
Min. = 5 ms
–
Max. = 15 ms
Reset time, alarm for pilot fuse failure at 0 to 1 x U
r
Min. = 15 ms
–
Max. = 30 ms
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
ABB
81