Figure 18:
Proposed test points for phase-to-phase loop of measuring element
Table 20:
Test points for phase-to-phase loop measuring element
Test point
R
X
Comment
P1
0
X1Fw
P2
R1Fw
X1Fw
P3
(0.8
∗
R1Fw
) +
RFPPFwZx
0.8
∗
X1Fw
P4
0.8
∗
RFPPFwZx
0.8
∗
RFPPFwZx
∗
tan
(
ArgLd
)
P5
RLd
0
P6
RFPPFwZx
0
OpLoadEnch
= Off
P7
0.5
∗
RLd
-0.5
∗
RLd
∗
tan (
ArgDir
)
P8
-0.5
∗
RFPPRvZx
X1Fw
P9
-0.8
∗
X1Fw
∗
tan
(
ArgNegRes
)
0.8
∗
X1Fw
1.
Inject the magnitude and angle of phase-to-phase voltage to achieve impedances at test points
P1, P2, …, P9.
2.
Test points P7 and P9 are intended to test the directional lines of impedance protection and
used to find directional accuracy for phase-to-phase faults.
3.
For each test point, observe that the start output signals START, STZx, STNDZx, STL1, STL2
and STPP are activated.
4.
Trip signals TRIP, TRZx, TRL1 and TRL2 will appear after set delay time of
tPPZx
if
OpModetPPZx
is set to On and
TimerSelZx
is set to Timers separated.
1MRK 506 377-UEN Rev. K
Section 10
Testing functionality by secondary injection
Railway application RER670
83
Commissioning manual
© 2017 - 2021 Hitachi Power Grids. All rights reserved
Содержание Relion 670 series
Страница 1: ...Relion 670 SERIES Railway application RER670 Version 2 2 IEC Commissioning manual...
Страница 2: ......
Страница 22: ...16...
Страница 26: ...20...
Страница 38: ...32...
Страница 48: ...42...
Страница 54: ...48...
Страница 58: ...52...
Страница 72: ...66...
Страница 178: ...172...
Страница 186: ...180...
Страница 187: ...181...