The
ActiveGroup
menu is located on the local HMI under
Main menu/Test /Function status/
Setting groups /ActiveGroup
The
ActiveGroup
menu is located on the PCM600 under
Main menu/Test/Function status/
Setting groups /ActiveGroup
3.
Connect the appropriate dc voltage to the corresponding binary input of the IED and observe
the information presented on the local HMI.
The displayed information must always correspond to the activated input.
4.
Check that the corresponding output indicates the active group.
Operating procedures for the PC aided methods of changing the active setting groups are
described in the corresponding PCM600 documents and instructions for the operators within
the SCS are included in the SCS documentation.
10.16.1.2
Completing the test
M11369-39 v4
Continue to test another function or end the test by changing the
TESTMODE
setting to
Off
. Restore
connections and settings to the original values, if changed for testing purposes.
10.17
Exit test mode
SEMOD53244-3 v6
The following procedure is used to return to normal operation.
After exiting the IED test mode, make sure that the MU is returned to normal mode.
1.
Navigate to the test mode folder.
2.
Change the
On
setting to
Off
. Press the 'E' key and the left arrow key.
3.
Answer
YES
, press the 'E' key and exit the menus.
Section 10
1MRK 506 377-UEN Rev. K
Testing functionality by secondary injection
158
Railway application RER670
Commissioning manual
© 2017 - 2021 Hitachi Power Grids. All rights reserved
Содержание Relion 670 series
Страница 1: ...Relion 670 SERIES Railway application RER670 Version 2 2 IEC Commissioning manual...
Страница 2: ......
Страница 22: ...16...
Страница 26: ...20...
Страница 38: ...32...
Страница 48: ...42...
Страница 54: ...48...
Страница 58: ...52...
Страница 72: ...66...
Страница 178: ...172...
Страница 186: ...180...
Страница 187: ...181...