15.9.5
Settings
Table 400:
SMAI_20_1 Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GlobalBaseSel
1 - 6
-
1
1
Selection of one of the Global Base Value
groups
DFTRefExtOut
InternalDFTRef
DFTRefGrp1
DFTRefGrp2
DFTRefGrp3
DFTRefGrp4
DFTRefGrp5
DFTRefGrp6
DFTRefGrp7
DFTRefGrp8
DFTRefGrp9
DFTRefGrp10
DFTRefGrp11
DFTRefGrp12
External DFT ref
-
-
InternalDFTRef
DFT reference for external output
DFTReference
InternalDFTRef
DFTRefGrp1
DFTRefGrp2
DFTRefGrp3
DFTRefGrp4
DFTRefGrp5
DFTRefGrp6
DFTRefGrp7
DFTRefGrp8
DFTRefGrp9
DFTRefGrp10
DFTRefGrp11
DFTRefGrp12
External DFT ref
-
-
InternalDFTRef
DFT reference
ConnectionType
Ph-N
Ph-Ph
-
-
Ph-N
Input connection type
AnalogInputType
Voltage
Current
-
-
Voltage
Analog input signal type
Table 401:
SMAI_20_1 Non group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
Negation
Off
NegateN
Negate3Ph
NeN
-
-
Off
Negation
MinValFreqMeas
5 - 200
%
1
10
Limit for frequency calculation in % of
UBase
Even if the
AnalogInputType
setting of a SMAI block is set to
Current
, the
MinValFreqMeas
setting is still visible. This means that
the minimum level for current amplitude is based on
UBase
. For
example, if
UBase
is 20000, the minimum amplitude for current is
20000 * 10% = 2000. This has practical affect only if the current
1MRK 505 288-UEN A
Section 15
Basic IED functions
481
Technical manual
Содержание Relion 650 Series REB650
Страница 1: ...Relion 650 series Busbar protection REB650 Technical manual ...
Страница 2: ......
Страница 36: ...30 ...
Страница 44: ...38 ...
Страница 58: ...52 ...
Страница 80: ...74 ...
Страница 84: ...78 ...
Страница 152: ...146 ...
Страница 278: ...272 ...
Страница 316: ...310 ...
Страница 432: ...426 ...
Страница 504: ...498 ...
Страница 518: ...512 ...
Страница 566: ...560 ...
Страница 567: ...561 ...