Function
Range or value
Accuracy
Apparent power, S
0.1 x U
r
< U < 1.5 x U
r
0.2 x I
r
< I < 4.0 x I
r
± 1.0% of S
r
at S ≤ S
r
± 1.0% of S at S > S
r
Apparent power, S Three phase
settings
cos phi = 1
± 0.5% of S at S > S
r
± 0.5% of S
r
at S ≤ S
r
Power factor, cos (φ)
0.1 x U
r
< U < 1.5 x U
r
0.2 x I
r
< I < 4.0 x I
r
< 0.02
12.2
Event Counter CNTGGIO
12.2.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Event counter
CNTGGIO
S00946 V1 EN
-
12.2.2
Functionality
Event counter CNTGGIO has six counters which are used for storing the number of
times each counter input has been activated.
12.2.3
Function block
CNTGGIO
BLOCK
COUNTER1
COUNTER2
COUNTER3
COUNTER4
COUNTER5
COUNTER6
RESET
VALUE1
VALUE2
VALUE3
VALUE4
VALUE5
VALUE6
IEC09000090_1_en.vsd
IEC09000090 V1 EN
Figure 153:
CNTGGIO function block
12.2.4
Signals
Table 263:
CNTGGIO Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of function
COUNTER1
BOOLEAN
0
Input for counter 1
COUNTER2
BOOLEAN
0
Input for counter 2
COUNTER3
BOOLEAN
0
Input for counter 3
COUNTER4
BOOLEAN
0
Input for counter 4
Table continues on next page
1MRK 505 288-UEN A
Section 12
Monitoring
341
Technical manual
Содержание Relion 650 Series REB650
Страница 1: ...Relion 650 series Busbar protection REB650 Technical manual ...
Страница 2: ......
Страница 36: ...30 ...
Страница 44: ...38 ...
Страница 58: ...52 ...
Страница 80: ...74 ...
Страница 84: ...78 ...
Страница 152: ...146 ...
Страница 278: ...272 ...
Страница 316: ...310 ...
Страница 432: ...426 ...
Страница 504: ...498 ...
Страница 518: ...512 ...
Страница 566: ...560 ...
Страница 567: ...561 ...