Table 417:
Analog input modules TRM
Terminal
TRM
6I + 4U
TRM
8I + 2U
TRM
4I + 1I + 5U
TRM
4I + 6U
X101-1, 2
1/5A
1/5A
1/5A
1/5A
X101-3, 4
1/5A
1/5A
1/5A
1/5A
X101-5, 6
1/5A
1/5A
1/5A
1/5A
X101-7, 8
1/5A
1/5A
1/5A
1/5A
X101-9, 10
1/5A
1/5A
0.1/0.5A
100/220V
X102-1, 2
1/5A
1/5A
100/220V
100/220V
X102-3, 4
100/220V
1/5A
100/220V
100/220V
X102-5, 6
100/220V
1/5A
100/220V
100/220V
X102-7, 8
100/220V
100/220V
100/220V
100/220V
X102-9, 10
100/220V
100/220V
100/220V
100/220V
Table 418:
Analog input modules AIM
Terminal
AIM
6I + 4U
AIM
4I + 1I + 5U
X103-1, 2
1/5A
1/5A
X103-3, 4
1/5A
1/5A
X103-5, 6
1/5A
1/5A
X103-7, 8
1/5A
1/5A
X103-9, 10
1/5A
0.1/0.5A
X104-1, 2
1/5A
100/220V
X104-3, 4
100/220V
100/220V
X104-5, 6
100/220V
100/220V
X104-7, 8
100/220V
100/220V
X104-9, 10
100/220V
100/220V
See the connection diagrams for information on the analog input
module variant included in a particular configured IED. The primary
and secondary rated values of the primary VT's and CT's are set for the
analog inputs of the IED.
16.2.2
Auxiliary supply voltage input
The auxiliary voltage of the IED is connected to terminals X420-1 and X420-2/3. The
terminals used depend on the power supply.
The permitted auxiliary voltage range of the IED is marked on top of the IED's LHMI.
Section 16
1MRK 505 288-UEN A
IED physical connections
500
Technical manual
Содержание Relion 650 Series REB650
Страница 1: ...Relion 650 series Busbar protection REB650 Technical manual ...
Страница 2: ......
Страница 36: ...30 ...
Страница 44: ...38 ...
Страница 58: ...52 ...
Страница 80: ...74 ...
Страница 84: ...78 ...
Страница 152: ...146 ...
Страница 278: ...272 ...
Страница 316: ...310 ...
Страница 432: ...426 ...
Страница 504: ...498 ...
Страница 518: ...512 ...
Страница 566: ...560 ...
Страница 567: ...561 ...