9.1.6
Monitored data
Table 89:
SDDRFUF Monitored data
Name
Type
Values (Range)
Unit
Description
3I0
REAL
-
A
Magnitude of zero
sequence current
3I2
REAL
-
A
Magnitude of negative
sequence current
3U0
REAL
-
kV
Magnitude of zero
sequence voltage
3U2
REAL
-
kV
Magnitude of negative
sequence voltage
9.1.7
Operation principle
9.1.7.1
Zero and negative sequence detection
The zero and negative sequence function continuously measures the currents and
voltages in all three phases and calculates: (see figure
)
•
the zero-sequence voltage 3U
0
•
the zero-sequence current 3I
0
•
the negative sequence current 3I
2
•
the negative sequence voltage 3U
2
The measured signals are compared with their respective set values
3U0<
and
3I0>
,
3U2<
and
3I2>.
The function enable the internal signal FuseFailDetZeroSeq if the measured zero-
sequence voltage is higher than the set value
3U0>
and the measured zero-sequence
current is below the set value
3I0<
.
The function enable the internal signal FuseFailDetNegSeq if the measured negative
sequence voltage is higher than the set value
3U2>
and the measured negative
sequence current is below the set value
3I2<
.
A drop off delay of 100 ms for the measured zero-sequence and negative sequence
current will prevent a false fuse failure detection at un-equal breaker opening at the
two line ends.
Section 9
1MRK 505 288-UEN A
Secondary system supervision
150
Technical manual
Содержание Relion 650 Series REB650
Страница 1: ...Relion 650 series Busbar protection REB650 Technical manual ...
Страница 2: ......
Страница 36: ...30 ...
Страница 44: ...38 ...
Страница 58: ...52 ...
Страница 80: ...74 ...
Страница 84: ...78 ...
Страница 152: ...146 ...
Страница 278: ...272 ...
Страница 316: ...310 ...
Страница 432: ...426 ...
Страница 504: ...498 ...
Страница 518: ...512 ...
Страница 566: ...560 ...
Страница 567: ...561 ...