10.3.3.5
Signals
Table 124:
BB_ES Input signals
Name
Type
Default
Description
QC_OP
BOOLEAN
0
Busbar earthing switch QC is in open position
QC_CL
BOOLEAN
0
Busbar earthing switch QC is in closed position
BB_DC_OP
BOOLEAN
0
All disconnectors on this busbar part are open
VP_BB_DC
BOOLEAN
0
Status for all disconnectors on this busbar part are
valid
EXDU_BB
BOOLEAN
0
No transmission error from any bay containing all
disconnectors on this busbar part
Table 125:
BB_ES Output signals
Name
Type
Description
QCREL
BOOLEAN
Switching of QC is allowed
QCITL
BOOLEAN
Switching of QC is forbidden
BBESOPTR
BOOLEAN
QC on this busbar part is in open position
BBESCLTR
BOOLEAN
QC on this busbar part is in closed position
10.3.3.6
Settings
The function does not have any settings available in Local HMI or Protection and
Control IED Manager (PCM600).
10.3.4
Interlocking for bus-section breaker A1A2_BS
10.3.4.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Interlocking for bus-section breaker
A1A2_BS
-
3
10.3.4.2
Functionality
The interlocking for bus-section breaker (A1A2_BS) function is used for one bus-
section circuit breaker between section 1 and 2 according to figure
can be used for different busbars, which includes a bus-section circuit breaker.
Section 10
1MRK 505 288-UEN A
Control
198
Technical manual
Содержание Relion 650 Series REB650
Страница 1: ...Relion 650 series Busbar protection REB650 Technical manual ...
Страница 2: ......
Страница 36: ...30 ...
Страница 44: ...38 ...
Страница 58: ...52 ...
Страница 80: ...74 ...
Страница 84: ...78 ...
Страница 152: ...146 ...
Страница 278: ...272 ...
Страница 316: ...310 ...
Страница 432: ...426 ...
Страница 504: ...498 ...
Страница 518: ...512 ...
Страница 566: ...560 ...
Страница 567: ...561 ...