Name of input
Type
Default
Description
Value when
activated
Value when
deactivated
IN14
BOOLEAN
0
Input 14
8192
0
IN15
BOOLEAN
0
Input 15
16384
0
IN16
BOOLEAN
0
Input 16
32768
0
The sum of the numbers in column “Value when activated” when all INx (where
1≤x≤16) are active that is=1; is 65535. 65535 is the highest boolean value that can be
converted to an integer by the B16I function block.
11.6
Boolean 16 to integer conversion with logic node
representation B16IFCVI
11.6.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Boolean 16 to integer conversion with
logic node representation
B16IFCVI
-
-
11.6.2
Functionality
Boolean 16 to integer conversion with logic node representation function B16IFCVI
is used to transform a set of 16 binary (logical) signals into an integer. The block input
will freeze the output at the last value.
1MRK 505 288-UEN A
Section 11
Logic
297
Technical manual