9.1.5
Settings
Table 87:
SDDRFUF Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
On
Operation Off / On
OpMode
Off
UNsINs
UZsIZs
UZsIZs OR UNsINs
UZsIZs AND
UNsINs
OptimZsNs
-
-
UZsIZs
Operating mode selection
3U0>
1 - 100
%UB
1
30
Operate level of residual overvoltage
element in % of UBase
3I0<
1 - 100
%IB
1
10
Operate level of residual undercurrent
element in % of IBase
3U2>
1 - 100
%UB
1
30
Operate level of neg seq overvoltage
element in % of UBase
3I2<
1 - 100
%IB
1
10
Operate level of neg seq undercurrent
element in % of IBase
OpDUDI
Off
On
-
-
Off
Operation of change based function
Off/On
DU>
1 - 100
%UB
1
60
Operate level of change in phase voltage
in % of UBase
DI<
1 - 100
%IB
1
15
Operate level of change in phase current
in % of IBase
UPh>
1 - 100
%UB
1
70
Operate level of phase voltage in % of
UBase
IPh>
1 - 100
%IB
1
10
Operate level of phase current in % of
IBase
SealIn
Off
On
-
-
On
Seal in functionality Off/On
USealln<
1 - 100
%UB
1
70
Operate level of seal-in phase voltage in
% of UBase
IDLD<
1 - 100
%IB
1
5
Operate level for open phase current
detection in % of IBase
UDLD<
1 - 100
%UB
1
60
Operate level for open phase voltage
detection in % of UBase
Table 88:
SDDRFUF Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GlobalBaseSel
1 - 6
-
1
1
Selection of one of the Global Base Value
groups
1MRK 505 288-UEN A
Section 9
Secondary system supervision
149
Technical manual
Содержание Relion 650 Series REB650
Страница 1: ...Relion 650 series Busbar protection REB650 Technical manual ...
Страница 2: ......
Страница 36: ...30 ...
Страница 44: ...38 ...
Страница 58: ...52 ...
Страница 80: ...74 ...
Страница 84: ...78 ...
Страница 152: ...146 ...
Страница 278: ...272 ...
Страница 316: ...310 ...
Страница 432: ...426 ...
Страница 504: ...498 ...
Страница 518: ...512 ...
Страница 566: ...560 ...
Страница 567: ...561 ...