1.
Check that the IED settings are appropriate, for example the start value and the
time delay.
2.
Supply the IED with three-phase voltages at their rated values and frequency 20
mHz under the set value
StartFrequency
, applying it for a time that is at least
10% longer than (
tDelay
+100 ms).
3.
Verify that the TRIP signal is active.
4.
Increase the frequency with a 40 mHz step, applying it until the TRIP signal
resets.
5.
Measure the reset time of the
TRIP
signal, and compare it with the technical data
of the function.
Verification of the low voltage magnitude blocking
1.
Check that the IED settings are appropriate, especially the
StartFrequency
and
the
tDelay
in SAPTUF, and the
GlobalBaseSel
and the
MinValFreqMeas
in the
SMAI preprocessing function.
2.
Supply the IED with three-phase voltages at rated values.
3.
Slowly decrease the magnitude of the applied voltage until the BLKDMAGN
signal appears.
4.
Note the voltage magnitude value and compare it with the value
MinValFreqMeas
x UBase / 100.
Where:
•
MinValFreqMeas
is a set value of the SMAI.
•
UBase is the value in the GBASVAL group identified by the setting
GlobalBaseSel
.
5.
Slowly decrease the frequency of the applied voltage, to a value below
StartFrequency
as explained in Section
"Verification of START value and time
.
6.
Check that the START signal does not appear.
7.
Wait for a time corresponding to (
tDelay
+100 ms), and check that the TRIP
signal does not appear.
8.
Slowly increase the magnitude of the applied voltages until the
BLKDMAGN
signal resets.
9.
Verify that the signal
START
appears and wait for a time at least equal to (
tDelay
+100 ms) to verify that also the signal TRIP becomes active.
6.7.1.2
Completing the test
Continue to test another function or end the testing by setting the parameter
TestMode
to
Off
under
Main menu/Tests/IED test mode/TESTMODE:1
. If another function
is tested, then set the parameter
Blocked
to
No
under
Main menu/Tests/Function test
modes/Frequency/SAPTUF(81,f<)/SAPTUF:X
for the function, or for each
individual function in a chain, to be tested next. Remember to set the parameter
Blocked
to
Yes
, for each individual function that has been tested.
Section 6
1MRK 502 049-UEN A
Testing functionality
90
Commissioning manual
Содержание REG650 ANSI
Страница 1: ...Relion 650 series Generator protection REG650 Commissioning manual...
Страница 2: ......
Страница 8: ......
Страница 20: ...12...
Страница 40: ...32...
Страница 42: ...34...
Страница 50: ...42...
Страница 120: ...112...
Страница 126: ...118...
Страница 142: ...134...
Страница 143: ...135...