They should change to logical 0 as follows:
•
Signal 3PH after about 25ms
•
Signal BLKU after about 50ms
•
Signal BLKZ after about 200ms
6.8.1.2
Measuring the operate value for the negative sequence function
1.
Simulate normal operating conditions with the three-phase currents in phase
with their corresponding phase voltages and with all of them equal to their rated
values.
2.
Slowly decrease the measured voltage in one phase until the BLKU signal
appears.
3.
Record the measured voltage and calculate the corresponding negative-
sequence voltage according to the equation.
Observe that the voltages in the equation are phasors.
3 U
2
×
U
L1
a
2
U
L2
a
+
×
U
L3
×
+
=
EQUATION707 V1 EN
(Equation 37)
Where:
U
L1
, U
L2
and U
L3
IEC00000275 V1 EN
= the measured phase voltages
2
3
3
1
0, 5
2
j
a
e
j
p
×
= ×
= -
+
IECEQUATION00022 V1 EN
4.
Compare the result with the set value (consider that the set value
3U2>
is in
percentage of the base voltage
UBase
) of the negative-sequence operating
voltage.
5.
. Then slowly increase the measured current in one phase
until the BLKU signal disappears.
6.
Record the measured current and calculate the corresponding negative-sequence
current according to the equation.
Observe that the currents in the equation are phasors.
2
1
2
3
2
3
L
L
L
I
I
a I
a I
×
=
+
×
+ ×
IECEQUATION00021 V1 EN
(Equation 40)
Where:
1
2
3
L
L
L
I
I and I
,
IECEQUATION00020 V1 EN
= the measured phase currents
1MRK 502 049-UEN A
Section 6
Testing functionality
95
Commissioning manual
Содержание REG650 ANSI
Страница 1: ...Relion 650 series Generator protection REG650 Commissioning manual...
Страница 2: ......
Страница 8: ......
Страница 20: ...12...
Страница 40: ...32...
Страница 42: ...34...
Страница 50: ...42...
Страница 120: ...112...
Страница 126: ...118...
Страница 142: ...134...
Страница 143: ...135...