IEC09000096-2-en.vsd
Tx
Tx
Rx
Rx
RJ-45
IED
PCM600
IEC09000096 V2 EN
Figure 2:
Point-to-point link between IED and PCM600 using a null-modem
cable
The following description is an example valid for standard PCs using Microsoft
Windows operating system. The example is taken from a Laptop with one Ethernet
interface.
Administrator rights are required to change the PC communication
setup. Some PCs have the feature to automatically detect that Tx
signals from the IED are received on the Tx pin on the PC. Thus, a
straight (standard) Ethernet cable can be used.
When a PC is connected to the IED and the setting
DHCPServer
is set to
On
via the
local HMI path
Main menu/Configuration/Communication/TCP-IP
configuration/ETHFRNT:1/DHCPServer
, the IEDs DHCP server for the front port
assigns an IP address for the PC. The PC must be configured to obtain its IP address
automatically as described in the following procedure.
1. Select
Search programs and files
in the
Start menu
in Windows.
Section 3
1MRK 502 049-UEN A
Starting up
24
Commissioning manual
Содержание REG650 ANSI
Страница 1: ...Relion 650 series Generator protection REG650 Commissioning manual...
Страница 2: ......
Страница 8: ......
Страница 20: ...12...
Страница 40: ...32...
Страница 42: ...34...
Страница 50: ...42...
Страница 120: ...112...
Страница 126: ...118...
Страница 142: ...134...
Страница 143: ...135...