Section 6
Testing functionality
6.1
Testing disturbance report
6.1.1
Introduction
The following sub-functions are included in the disturbance report function:
•
Disturbance recorder
•
Event list
•
Event recorder
•
Trip value recorder
•
Indications
If the disturbance report is set on, then its sub-functions are also set up and so it is not
possible to only switch these sub-functions off. The disturbance report function is
switched off (parameter
Operation
=
Off
) in PCM600 or the local HMI under
Main
menu/Settings/IED Settings/Monitoring/Disturbance report/DRPRDRE:1
.
6.1.2
Disturbance report settings
When the IED is in test mode, the disturbance report can be made active or inactive.
If the disturbance recorder is turned on during test mode, recordings will be made.
When test mode is switched off all recordings made during the test session are cleared.
Setting
OpModeTest
for the control of the disturbance recorder during test mode are
located on the local HMI under
Main menu/Settings/IED Settings/Monitoring/
Disturbance report/DRPRDRE:1
.
6.2
Identifying the function to test in the technical
reference manual
Use the technical manual to identify function blocks, logic diagrams, input and output
signals, setting parameters and technical data.
1MRK 502 049-UEN A
Section 6
Testing functionality
43
Commissioning manual
Содержание REG650 ANSI
Страница 1: ...Relion 650 series Generator protection REG650 Commissioning manual...
Страница 2: ......
Страница 8: ......
Страница 20: ...12...
Страница 40: ...32...
Страница 42: ...34...
Страница 50: ...42...
Страница 120: ...112...
Страница 126: ...118...
Страница 142: ...134...
Страница 143: ...135...