Diagnostics
79
Installation problems
Verify all the connections on the module:
• Check that the DeviceNet cables are connected to terminal
block X1 as described in chapter
Electrical installation
.
• Check that an external voltage of 24 V DC is applied to
terminals X1:1 and X1:5.
• Check that the RDNA-01 module is properly inserted into the
option slot.
• Check the fastening of the RDNA-01 module with the 2 screws.
Drive setup
The fieldbus parameter group is not shown on the panel:
• Enable the RDNA-01 by setting the appropriate drive
parameter.
The RDNA-01 is using default values:
• Verify that the fieldbus parameter group is set up correctly. If so,
turn off and on the power to the drive or issue a ‘Fieldbus
Adapter parameter refresh’ command. This will make the
module re-read its setup parameters.
Drive actual values can be read, but the control commands (start/
stop or reference) do not go through:
• Check that the control location parameters of the drive are set to
use the RDNA-01 as the source of the required command.
• Check that the drive is in REMOTE control.
PLC programming
The PLC program is beyond ABB Drives support. Contact the
manufacturer for assistance.
Scanner fault indications
Refer to scanner documentation.
Содержание RDNA-01
Страница 1: ...ABB Drives User s Manual DeviceNet Adapter Module RDNA 01 ...
Страница 2: ......
Страница 4: ......
Страница 6: ...Safety instructions 6 ...
Страница 10: ...Table of contents 10 ...
Страница 14: ...Introduction 14 ...
Страница 20: ...Quick start up guide 20 Add drive to network in RSNetWorx for DeviceNet Configure device MAC address ...
Страница 30: ...Mechanical installation 30 ...
Страница 52: ...Communication profiles 52 ...
Страница 80: ...Diagnostics 80 ...
Страница 84: ...Definitions and abbreviations 84 ...
Страница 87: ......