Quick start-up guide
23
Mechanical and electrical installation
• Insert the RDNA-01 into its specified slot in the drive.
• Fasten the screws.
• Plug the fieldbus connector into the module.
Drive configuration
Note:
Configuring the drive for communication with the module is
dependent on the drive type. Refer to the
Firmware Manual
of the
drive for detailed information on configuring the drive to use the
communication module.
• Power up the drive.
• Configure drive to enable module. With an ACS550 drive, set
parameter 98.02 COMM PROT SEL to EXT FBA. With an
ACS800 drive, set parameter 98.02 COMM. MODULE LINK to
FIELDBUS.
• Verify that FBA TYPE is DEVICENET. On the ACS800 drive,
this is parameter 51.01.
• With ACS800, set parameter 98.07 COMM PROFILE according
to your assembly instance selection. See the table in section
communication profiles for more information. This is not needed
with ACS550.
• Configure drive to accept Start/Stop, Direction, Reference, Run
Enable and Fault Reset from module. Examples of appropriate
values on the ACS800 are shown in the following tables.
• Configure module via fieldbus configuration groups for desired
network characteristics. Examples of appropriate values on the
ACS800 are shown in the following tables.
• Initiate a “Fieldbus adapter parameter refresh” by setting
parameter 51.27 FBA PAR REFRESH.
Содержание RDNA-01
Страница 1: ...ABB Drives User s Manual DeviceNet Adapter Module RDNA 01 ...
Страница 2: ......
Страница 4: ......
Страница 6: ...Safety instructions 6 ...
Страница 10: ...Table of contents 10 ...
Страница 14: ...Introduction 14 ...
Страница 20: ...Quick start up guide 20 Add drive to network in RSNetWorx for DeviceNet Configure device MAC address ...
Страница 30: ...Mechanical installation 30 ...
Страница 52: ...Communication profiles 52 ...
Страница 80: ...Diagnostics 80 ...
Страница 84: ...Definitions and abbreviations 84 ...
Страница 87: ......