Fault tracing
51
Fault tracing
What this chapter contains
This chapter lists the LEDs of the RBIP-01 BACnet/IP Router Module and describes
their funtion.
LED indications
The RBIP-01 BACnet/IP Router Module is equipped with the following LEDs:
LED name
Color
Function
POWER
Green
Off
- No power
Steady green
- Power is connected
MS/TP TxD
Yellow
Flashing yellow
- Module is transmitting data to MS/
TP network
MS/TP RxD
Yellow
Flashing yellow
- Module is receiving data from MS/
TP network
STATUS
Green/
Red/
Orange
Steady green
- Reset switch is pressed and held
Flashing green
- Normal operation mode or commis-
sioning
Alternating green/red
- DHCP server activated
Steady orange
- Lit for approximately 25 seconds in
starting phase after power-up. When the steady or-
ange LED is lit, the router module is starting up and
does not respond during boot.
Flashing orange
- Flashing after start-up phase;
module is running with factory settings and needs to
be commissioned
Flashing red
- Bus errors on MS/TP bus, for exam-
ple, framing errors
Steady red
- Module is performing reset
Network LED
Orange
Orange network LED is located to the right of RJ-45
network connector.
Off
- 10 MBit/s connection
On
- 100 MBit/s connection
Network LED
Green
Green network LED is located to the left of RJ-45 net-
work connector.
Off
- Module cannot detect a link
On
- Module has detected a link
Flashing green
- Activity on the link