User interface
34
MS/TP submenu
When you select the
MS/TP
submenu, the
MS/TP Settings
page opens. It provides
the settings for BACnet MS/TP.
MS/TP Settings page
If your BACnet router works in MS/TP, give the following settings:
MS/TP Settings
Description
Baud Rate
The baud rate in the MS/TP network
The potential values are: 9600, 19200, 38400, 57600, 76800 and
115200 bit/s. The default value is 38400.
Note that the 57600 and 115200 baud rates are not BACnet standard
baud rates and all MS/TP implementations may not support them.
MAC Address
The MAC address of the router module in the MS/TP network. The
router module acts as an MS/TP master node.
The value is valid from 0 to 127 and the default value is 0.
Network Number
The network number of your local MS/TP network. The network number
must be unique within the entire network.
The network number is valid in the range from 1 to 65.535. The default
value is 2.