User interface
35
Save
button
The
Save
button temporarily saves the changes made on this page.
Note:
You must save your changes before switching to another configuration page.
If you switch to another page without saving, the settings remain unchanged.
Note:
You must activate the configuration before restarting the router module.
Activating the configuration saves all settings permanently. If you restart the router
module without activating the configuration, the old configuration remains active and
the changes are lost.
For activating your settings, see section
Token Timeout
The Token timeout is the minimum time without a DataAvailable or
ReceiveError event that a node must wait for a remote node to begin
using a token or replying to a Poll For Master frame.
The valid range is from 20 to 100 milliseconds, and the default value is
20 milliseconds.
Reply Timeout
The Reply timeout is the minimum time without a DataAvailable or
ReceiveError event that a node must wait for a station to begin replying
to a confirmed request.
The valid range is from 200 to 300 milliseconds, and the default value is
250 milliseconds.
Max Master
The Max_Master property specifies the highest possible address for
master nodes.
The valid range is from 1 to 127, and the default value is 127.
Max Info Frames
The Max_Info_Frames property specifies the maximum number of
information frames the node may send before it must pass the token to
the next node.
The valid range is from 1 to 127, and the default value is 1.
MS/TP Settings
Description
Содержание RBIP-01
Страница 1: ...ACH550 User s Manual BACnet IP Router Module RBIP 01 ...
Страница 4: ......
Страница 6: ...Safety instructions 6 ...
Страница 16: ...Overview 16 ...
Страница 52: ...Fault tracing 52 ...
Страница 56: ...BACnet Protocol Implementation Conformance Statement PICS 56 ...
Страница 57: ......