![ABB RBIP-01 Скачать руководство пользователя страница 33](http://html.mh-extra.com/html/abb/rbip-01/rbip-01_user-manual_2761033.webp)
User interface
33
FD submenu
When you select the
FD
submenu, the
Foreign Device Settings
page opens. It
provides settings for a foreign device (FD). In this mode, the router module acts as a
foreign device to retrieve broadcast messages from an external BBMD.
Foreign Device Settings page
If your BACnet/IP router works as a foreign device, fill in the following settings:
Save
button
The
Save
button temporarily saves the changes made on this page.
Note:
You must save your changes before switching to another configuration page.
If you switch to another page without saving, the settings remain unchanged.
Note:
You must activate the configuration before restarting the router module.
Activating the configuration saves all settings permanently. If you restart the router
module without activating the configuration, the old configuration remains active and
the changes are lost.
For activating your settings, see section
Foreign Device
Settings
Description
IP Address BBMD
The IP address of the external BBMD to connect to
UDP Port
The UDP port which is used for BACnet communication in the external
BACnet - subnetwork.
This value is in decimal notation and the default value is 47808 dec.
(0xBAC0 hex.).
Re-register Time
The interval within which the foreign device must re-register at the
external BBMD. The value is in seconds and the default value is 10s.
Содержание RBIP-01
Страница 1: ...ACH550 User s Manual BACnet IP Router Module RBIP 01 ...
Страница 4: ......
Страница 6: ...Safety instructions 6 ...
Страница 16: ...Overview 16 ...
Страница 52: ...Fault tracing 52 ...
Страница 56: ...BACnet Protocol Implementation Conformance Statement PICS 56 ...
Страница 57: ......