![ABB ProKiln GAC400 Скачать руководство пользователя страница 23](http://html1.mh-extra.com/html/abb/prokiln-gac400/prokiln-gac400_operating-instruction_4693066023.webp)
ProKiln GAC400
PROBE GAS SAMPLING SYSTEM | OI/GAC400-EN REV. A
23
Water Panel
The probe is made from high temperature resistant steel but, because of the extreme high temperature of a kiln inlet, it needs a
cooling system to sustain the operation.
The probe water panel serves to provide and monitor the cooling water supply. The water panel contains the water circulation pump,
which circulates the cooling water in a pressure-open system operating at ambient pressure level. A 300 l (approx. 80 gal US) water
tank serves as both a water and temperature buffer for the water-cooling system.
The water panel can be installed directly connected to the cooling panel or it can be installed within a maximum distance of 5 m
(16 ft 5 in) to the cooling panel.
The completely open system monitors the following parameters:
• Water pump operation
• Water tank temperature
• Water tank water levels
• Cooling water flow rate
Figure 8: Water panel
Pos.
Component
Function
1
Water pump
Re-circulate the cooling water
2
Temperature sensor (not shown in picture)
Measures the temperature in the water tank which controls the heat exchanger fan operation
3
Water-return from probe
Water from probe 1
″
union connects to the heat exchanger by a 1
″
hose
4
Water tank
Holding tank for water and temperature buffer for cooling system. Volume 300 litters.
5
Level sensor
Detects the water level in the water tank
6
Solenoid valve
Water refill of tank
7
Electrical panel
• Contain electrical connection and local I/O panel
• Power breakers for pump and cooler fans
8
Water forward to probe
Outlet union 1
″
for water cooling of probe
9
Water flow meter
Measures the water flow as it returns from the probe and continues to the heat exchanger
0
Water forward from cooling panel
Connects 1
″
hose stub to the heat exchanger
3
8
9
1
6
5
j
4
7