11
35
1.5.2 Fault finding chart
FAULT CAUSE REMEDY
Spring does not get
charged
Closing of breaker
does not take place
although there is an
indication that the
springs are
charged.
Breaker
continuously opens
and closes.
Motor has wrong or no
operating voltage.
Motor shaft broken.
Motor gear damaged.
The latch for the tripping
device does not function.
Disconnection in the
wires.
Micro-switch arm wrongly
adjusted.
Breaker closes then
opens again.
Operating coils does not
operate.
The toggle joints of the
mechanism are incorrectly
adjusted.
Wrong wiring of the
auxiliary circuit.
Wrongly adjusted
clearances of opening
magnets armature.
Anti pumping relay wrong
or faulty.
Measure voltage on
the motor leads.
Change motor.
Change motor.
Change mechanism.
Check by measuring.
Adjust the micro-
switch operating arm.
Measure the voltage
adjust the coils
adjustment screw.
Check the springs.
Adjust the toggle
joints.
Check the wiring as
per schematic
drawing.
Adjust the opening
magnet.
Change relay.
Содержание OVB-SDB
Страница 26: ......
Страница 49: ...Fig 1 Lifting of Circuit Breaker 50 ...
Страница 52: ...Fig 4 Breaker Pole Assembly Refer legend on pg 48 53 ...
Страница 53: ...Fig 5 Schematic Circuit Diagram 54 ...
Страница 55: ...15029 15027 15028 Fig 7 ESH Mechanism with Cabinet Refer legend on pg 49 56 ...
Страница 56: ...Fig 8 ESH Mechanism with operating rod and lever Refer Legend on pg 49 15000A 15036 15035 15034 57 ...
Страница 60: ...Disconnect the motor power supply 7 Fig 15 Motor 61 ...
Страница 62: ...Fig 18 The Magnetic Actuator 63 ...
Страница 63: ...Notes ...