36
1.5.3 Replacement of operating coil
Refer Fig.9 to 12, (page no 58 to 59) indicates the mounting arrangement for
closing coils and the tripping coils.
1.5.4. Replacement of micro-switch
Refer fig. 16 & 17, (page no. 62) indicates the
mounting arrangement for micro-switch.
1.5.5 Replacement of motor
Refer fig.14 & 15,(page no. 60 & 61) indicates the mounting
arrangement for motor.
1.5.6 Replacement of operating mechanism
The operating mechanism shall be replaced in the following manner.
a. Disconnect the linkage of the operating mechanism to the main shaft
b. Disconnect the electrical connection.
c. Loosen screws that fix the operating mechanisminside the cabinet.
d. Take out the operating mechanism and fix new one.
e. Reconnect the electrical connections and the linkage of the main shaft. After fixing
the operating mechanism the following check shall be carried out.
f. Charge the closing spring.
g. Close the breaker.
h. If required then adjust the micro-switch for proper operation.
i. Check the breakers with the auxiliary supply connect while charging at minimum
operating voltage of the motor.
j. Take few operations for the new mechanism.
k. Seal various lock nuts of various settings with red paint.
1.5.7 Recommended spares parts
The following spares shall be kept to take care of any contingency
Sr. No Name of parts Part No.
1 Spring charging motor 15032
2 Tripping/closing coils 15030(A,B)
3 Micro-switches 15033
4 Auxiliary switches 15027
5 Shock absorber 15007
6 Operating box assembly 15012
7 Opening transmission lever 15010
8 Closing transmission lever 15011
9 Operating Mechanism 15000A
Содержание OVB-SDB
Страница 26: ......
Страница 49: ...Fig 1 Lifting of Circuit Breaker 50 ...
Страница 52: ...Fig 4 Breaker Pole Assembly Refer legend on pg 48 53 ...
Страница 53: ...Fig 5 Schematic Circuit Diagram 54 ...
Страница 55: ...15029 15027 15028 Fig 7 ESH Mechanism with Cabinet Refer legend on pg 49 56 ...
Страница 56: ...Fig 8 ESH Mechanism with operating rod and lever Refer Legend on pg 49 15000A 15036 15035 15034 57 ...
Страница 60: ...Disconnect the motor power supply 7 Fig 15 Motor 61 ...
Страница 62: ...Fig 18 The Magnetic Actuator 63 ...
Страница 63: ...Notes ...