11
23
6.4 Maintenance Schedule
Maintenance
operation
Carry out the
general
inspection
(For details, refer
clause 6.5)
Measure the
insulation
resistance
Lubricate the
sliding points
Carrying out the
operating
mechanism
maintenance
Complete
overhaul
Connection of
electronics
circuit
Cleaning of
electronic circuit
Retention of
spring circlips and
spring washer
Installation in normal
ambient
2 years 1 year
4 years 2 years
2 years 1 year
Five years or every Three years or every
10000 operations 5000 operations
Ten years or every 10000 Five years or every
operations 10000 operations
2 years 1 year
2 years 1 year
2 years 1 year
Installation in dusty
or polluted ambient
Содержание OVB-SDB