Note
For OmniCore, a safety input that is initiated must remain active for at least 100
ms.
Stop category configuration for OmniCore
The stop category for the safety input can be configured, see
Technical reference
manual - System parameters
.
Description
System paramet-
er
Function
Safety inputs
Category1AS
can be used to configure the protective
stop in automatic mode either as stop category 0 or
category 1. The default configuration is
TRUE
(stop
category 1).
Category1AS
Automatic Stop
Category1ES
is used to configure the emergency stop
in automatic and manual mode. The default configura-
tion is
FALSE
(stop category 0). The input is connected
to the emergency stop on the FlexPendant and can
also be connected to external devices.
Category1ES
i
Emergency Stop
i
In RobotWare 7.0 there are two values for the safety input
Emergency Stop
, named
Category1EES
(for external emergency stop) and
Category1LES
(for emergency stop on FlexPendant). These are
merged in RobotWare 7.1 into
Category1ES
.
Product manual - OmniCore C90XT
23
3HAC073706-001 Revision: D
© Copyright 2020-2021 ABB. All rights reserved.
1 Safety
1.3.1 Protective stop and emergency stop
Continued
Содержание OmniCore C90XT
Страница 1: ...ROBOTICS Product manual OmniCore C90XT ...
Страница 2: ...Trace back information Workspace 21A version a14 Checked in 2021 03 30 Skribenta version 5 4 005 ...
Страница 50: ...This page is intentionally left blank ...
Страница 350: ...This page is intentionally left blank ...
Страница 354: ...This page is intentionally left blank ...
Страница 412: ...This page is intentionally left blank ...
Страница 444: ...This page is intentionally left blank ...
Страница 448: ......
Страница 449: ......