![ABB LEANtouch 6x36/30M-500 Series Скачать руководство пользователя страница 64](http://html.mh-extra.com/html/abb/leantouch-6x36-30m-500-series/leantouch-6x36-30m-500-series_product-manual_2736064.webp)
64
January 2005
ABB i-bus
®
EIB
ABB Powernet EIB
LEANtouch (monochrome),
SMARTtouch (monochrome, colour)
Type: 6x36/30M(-500), 6x36/100x(-500), 6x36/100CB
Functional description: Alarm
function
The panel offers the possibility of
displaying up to 10 different alarm
messages. The parameter “Number
of alarm messages” defines the
required number.
Each alarm message has its own
communication object “Alarm 1” to
“Alarm 10”. The communication
objects can either be 1 bit or 14 byte.
The setting “Type of the alarm object”
sets the size of the object. Each alarm
object can thus be set individually.
The alarm function can be used in
combination with the inputs of the
monitoring function (see page 18) or
on its own. In combination with the
monitoring function, the inputs and
the alarm objects must be linked via
internal group addresses.
If a telegram e.g. an ON telegram is
received at an alarm object, a window
is opened in the screen of the panel,
in which the alarm text is displayed.
The alarm text can be freely entered in
the panel software. The panel
simultaneously triggers a signal tone.
The duration of the signal tone can be
set and it can also be deactivated.
All alarm messages which occur or
have occurred can be displayed via a
further window in the panel. The
window is opened by pressing the
“Extras” button followed by “Alarm
messages/Fault messages”. All
alarm and fault messages are
displayed with the date, time and
acknowledgement.
The acknowledgement of an alarm
message is carried out via the “OK”
button in the alarm text window. If the
setting “Send zero at acknowledge”
has been activated with “yes” for a
1-bit alarm object, the group address
that is linked with the alarm object is
sent on the bus with the value “0”.
In the case of a 14-byte alarm object,
an individual acknowledgement text
(max. 13 characters) can be sent with
the acknowledgement.
Via the acknowledgement object
“Acknowledge global”, a group
address is sent as soon as an
acknowledgement has been carried
out at one of the alarm objects.