Type: 6x36/30M(-500), 6x36/100x(-500), 6x36/100CB
Parameters: Room thermostat
The default setting for the values
is printed in bold type.
General:
– Control heating
Active
– Control additional heating
Inactive
Active
– Control cooling
Inactive
Active
– Operation mode after reset
Comfort
Standby
Night
Frost protection
– Cyclic sending of actual value and
14:50
setpoint in mm.ss (03:00…60:00)
– Change of actual temp. for
Inactive / 0.2 K / 0.4 K / 0.6 K / 0.8 K /
automatic sending
1.0 K / 1.5 K / 2.0 K
– Automatic shading (see also
Inactive
setpoints)
Active
– Party time (extension of comfort
Inactive / 30 min / 1 h / 1.5 h / 2 h /
mode)
2.5 h / 3 h / 4 h
– Display heating/cooling is active
If operation mode is active
At heating resp. cooling
– Group master operation mode
Inactive
Active
– Disable frost/heat protection manually
Locked
(extension of comfort mode)
Free
– Actual value survey
Internal
External
– Toggle between heating and
automatic
cooling
via object
– Offset value in K x 0.1 K
0
Setpoints general:
– Area for manual setpoint setting
Disabled / +- 1K / +- 3K / +- 5K
– Maximum increasing of setpoint
3
at heating in K (0…5)
Only for cooling:
– Maximum lowering of setpoint
3
at cooling in K (0…5)
– Send actual setpoint at change
Inactive
Active
– Manual setpoint setting
Reset at receiving of base
setpoint
Hold at receiving of base
setpoint
Only for shading:
– Shading setpoint
Comfort tempe 2K
Comfort tempe 4K
Comfort tempe 6K
Comfort tempe 8K
– Temperature display at
Act. setpoint
setpoint adjustment
Base setpoint