Type: 6x36/30M(-500), 6x36/100x(-500), 6x36/100CB
Setpoints heating:
– Base setpoint in °C (16…31)
21
Comfort temperature heating
– Lowering standby operation heating
2
in K (1…15)
– Lowering night operation heating
4
in K (1…15)
– Setpoint frost protection
7
in °C (4…10)
– Level distance from the base level
3
to the additional level in K
Controlling/Control value heating:
– Output of control value
continuously
switched
– Control type
Two-position controller
PI controller
Only for two-position controller:
– Hysteresis
0.3K / 0.5K / 0.7K / 1K / 1.5K / 2K
– Lowering of hysteresis
Inactive
0.2 K/min
0.1 K/min
0.06 K/min
0.04 K/min
0.03 K/min
0.02 K/min
– Cycle time of the control value in mm:ss 14:50
(03:00…60:00)
Only for continuous controller:
– Change for automatic sending of
Inactive / 2% / 5% / 10%
control value
Only for PI controller:
– Control parameters
via installation type
free setting of parameters
Only for installation type:
– Type of heating system
Warm water heating (1.5K/100min)
Electric heating (1.5K/50min)
Floor heating (4K/200min)
Only for free parameterisation:
– Proportional area
1.0K / 1.5K / 2.0K / 2.5K / 3K / 4K /
6K / 8K / 10K
– Reset time in min.
I part inactive / 10 min / 20 min /
30 min / … / 100 min / … / 240 min
Only for switched controller:
– PWM cycle
3min / 5min / 10min / 15min / 20min /
30min / 40min / 50min / 60min
– PWM cycle is 0% up to control value
0% / 10% / 20% / 30%
– PWM cycle is 100% up to control value
70% / 80% / 90% / 100%
– Effective mode
Normal
Inverted
Only for additional heating:
– Hysteresis (one-sided)
0.3K / 0.5K / 0.7K / 1.0K / 1.5K / 2.0K
– Cycle time for automatic sending of the 14:50
control value e in mm:ss (03:00…60:00)
– Control value type
switched
quasi contin. (1 Byte: 0% or 100%)
– Effective mode
Normal
Inverted
Parameters: Room thermostat
The default setting for the values
is printed in bold type.