![ABB LEANtouch 6x36/30M-500 Series Скачать руководство пользователя страница 60](http://html.mh-extra.com/html/abb/leantouch-6x36-30m-500-series/leantouch-6x36-30m-500-series_product-manual_2736060.webp)
60
January 2005
ABB i-bus
®
EIB
ABB Powernet EIB
LEANtouch (monochrome),
SMARTtouch (monochrome, colour)
Type: 6x36/30M(-500), 6x36/100x(-500), 6x36/100CB
Only for cooling:
Setpoints cooling:
– Dead zone between heating and
4
cooling in K (1…8)
– Increasing standby operation cooling
2
– Increasing night operation cooling
4
– Setpoint heat protection
Cooling switched off
30°C
35°C
40°C
44°C
Controlling/Control value cooling:
– Output of control value
continuously
switched
– Control type
Two-position controller
PI controller
Only for two-position controller:
– Hysteresis
0.3K / 0.5K / 0.7K / 1.0K / 1.5K / 2.0K
– Lowering of hysteresis
Inactive
0.2 K/min
0.1 K/min
0.06 K/min
0.04 K/min
0.03 K/min
0.02 K/min
– Cycle time of the control value in
04:46
mm:ss (03:00…60:00)
– Effective mode
Normal
Inverted
Only for PI controller:
– Control parameters
via installation type
free setting of parameters
– Type of cooling system
Cooling ceiling (5K/240min)
SplitUnit/Fan cooling (4K/90min)
– PWM cycle
3min / 5min / 10min / 15min / 20min /
30min / 40min / 50min / 60min
– PWM cycle is 0% up to control value
0% / 10% / 20% / 30%
– PWM cycle is 100% up to control value 70% / 80% / 90% / 100%
– Effective mode
Normal
Inverted
Only for free parameterisation:
– Proportional area
1.0K / 1.5K / 2.0K / 2.5K / 3K / 4K /
6K / 8K / 10K
– Restet time in min.
I part inactive / 10 min / 20 min / …
100 min / … / 200 min / 240 min
Only for continuous controller:
– Cycle time of the control value in mm:ss 04:46
(03:00…60:00)
– Effective mode
Normal
Inverted
– Change for automatic sending of
Inactive / 2% / 5% / 10%
control value
Parameters: Room thermostat
The default setting for the values
is printed in bold type.