![ABB LEANtouch 6x36/30M-500 Series Скачать руководство пользователя страница 15](http://html.mh-extra.com/html/abb/leantouch-6x36-30m-500-series/leantouch-6x36-30m-500-series_product-manual_2736015.webp)
January 2005
15
ABB i-bus
®
EIB
ABB Powernet EIB
LEANtouch (monochrome),
SMARTtouch (monochrome, colour)
Type: 6x36/30M(-500), 6x36/100x(-500), 6x36/100CB
If the indoor and outdoor temperature
should be displayed simultaneously,
the corresponding point on the
display changes every 5 s.
The panel can display the date and
time. The display can be carried out in
the German format (TT.MM.JJJJ; 24h)
or in the English format (MM.TT.JJJJ;
12h).
The panel can send and receive the
date and time on the EIB via the two
3-byte communication objects “Date”
and “Time”. The panel can thus act as
a master clock for other EIB devices
or as an extension unit. In its function
as an extension unit, the date and
time can e.g. be sent by an EIB DCF-
77 receiver on the bus. By default, the
date and time are neither sent nor
received.
If the date and the time should be
displayed on the panel, the
corresponding display switches
between date and time every 5 s.
The panel has an info page, an alarm
clock and a timer. All three functions
can be activated in the basic settings.
Address page
The contact person, company,
telephone, fax and email of the
electrical company which carried out
the installation can be stored on the
address page. In the event of
changes, the customer (end user)
does not need to search in his
documentation to find the right contact
person. He will find all the relevant
data directly in the panel.
System settings
The system settings are not enabled
as standard. This means that a four
digit code (by default 0000) must be
entered on the display so that
changes can be carried out. Only
authorised personnel may therefore
view and modify the system settings.
It is possible however to enable the
system settings in principle e.g. in
enclosed rooms with users who are
permitted to carry out settings. The
system settings can also be fully
disabled.
Caution:
If you disable the system settings
completely, the menu item
“Commissioning” on the panel can no
longer be selected. In this case, you
must carry out a long operation at the
bottom left of the display and thereby
switch on the mains voltage. The
menu item “System” becomes visible
and the panel can e.g. be
commissioned with the multimedia/
SD card.
If the system settings are saved with
the help of a code, the code is defined
via the parameter “Code for system
settings”.
The following settings can be carried
out in the system settings on the
display:
– Change date
– Change time
– Display lighting
– Volume
– Contrast / brightness
– Signal tones
– Alarm messages
– Timer / alarm clock
– Incorrect input
– Push button click
– Touchscreen adjustment
– Commissioning
– EIB programming
– Reading multimedia/SD card
(see also diagram for modifying