5.3.4.2
General commands in control direction
GUID-83F365BB-62F9-4E34-A291-73430639B898 v2
Table 63:
General commands in control direction
INF
Semantics
Supported
16
Auto-recloser on/off
Yes
17
Teleprotection on/off
Yes
18
Protection on/off
Yes
19
LED reset
Yes
23
Activate characteristic 1
Yes
24
Activate characteristic 2
Yes
25
Activate characteristic 3
Yes
26
Activate characteristic 4
Yes
5.3.4.3
Generic functions in control direction
GUID-1EF480C8-5809-43C0-9EF1-D87AF46BEBFE v2
Table 64:
Generic functions in control direction
INF
Semantics
Supported
240
Read headings of all defined groups
No
241
Read values or attributes of all entries of one
group
No
243
Read directory of a single entry
No
244
Read value or attribute of a single entry
No
245
General interrogation of generic data
No
248
Write entry
No
249
Write entry with confirmation
No
250
Write entry with execution
No
251
Write entry abort
No
5.3.5
Basic application functions
GUID-13D3DF1D-2C9C-4933-BF4D-6AFBA5A96E82 v3
Table 65:
Basic application functions
Supported
Test mode
Yes
Blocking of monitor direction
No
Disturbance data
Yes
Generic services
No
Private data
Yes
Section 5
1MRK 511 394-UEN A
Interoperability
60
670 series 2.2 IEC
Communication protocol manual